Inspections for the day of: Tuesday, March 20, 2007.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-00888 Electrical Rough-In3/20/20073/20/20073/20/2007 3:16:58 PMPPASS
Phone #: ###-#### corr made, ric ok
ELE07-00878 Temporary Service3/20/20073/20/20073/20/2007 2:34:22 PMPFAIL
Scheduled by a contractor via Hello! on 3/20/2007 at 10:28:37 AM. Contact: ###-####. called contr, left corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection, 110.12(C) there shall be no broken parts-50a recpt, there shall be no contamination-inside panel, there shall be no damaged parts-gec, BCC job id sticker shall be posted
ELE07-00312 Final3/20/20073/20/20073/20/2007 1:53:17 PMPPASS
paul; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok to final, signed occ card
ELE07-00185 Final3/20/20073/20/20073/20/2007 1:05:35 PMPFAIL
ready for final, please contact Patrick, thank you Phone #: ###-#### called contr, left corr notice, nec 352.30(A) rnc shall be strapped within 3' of termination, 408.4 & 110.22 circuit directory shall be clear concise and specific to its purpose, 110.26(A) work space shall be provided about inside and outside panels as code states, BCC job shall be completed with all devices installed- rear outlet
ELE06-01263 Final3/20/20073/20/20073/20/2007 12:19:50 PMPPASS
Scheduled by a contractor via Hello! on 3/20/2007 at 7:16:45 AM. Contact: ###-####. called contr to chg stranded to solid #8 to bond motors, ok to final
ELE07-00185 Electrical Rough-In3/20/20073/20/20073/20/2007 11:20:12 AMPCANC
Please contact Miles, thank you Phone #: ###-#### Inspection cancelled from web by: Wendy Waters
ELE07-00901 Conference3/19/20073/20/20073/20/2007 10:36:05 AMADONE
please call 30 mintues prior so we can meet you out there. Phone #: ###-#### reviewed relocating each apt panel and looked at service feeders in basement areas, said no violations shall be retained and to be sure 4-wire to ranges
ELE07-00903 Electrical Rough-In3/19/20073/20/20073/20/2007 9:40:39 AMAPASS
jessie; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ri ok, see final
ELE07-00903 Final3/20/20073/20/20073/20/2007 9:40:10 AMAPASS
jessie; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok to final
ELE05-01204 Final3/19/20073/20/20073/20/2007 9:11:35 AMAFAIL
Mike; Phone #: ###-#### Internet Inspection Request from: Stacie Backus met owner, left corr notice, nec 210.8(A) (6) & (2) & (3) kitchen and garage and outside receptacles shall be gfci protected, 408.4 circuit directory shall be clear, concise, and complete for each circuit, 422.31(B) water heater and furnace shall have disconnects, 110.3(B) equipment shall be installed per listing and labelling- no open grounds or reverse polarity, 210.12 arc fault protection shall be provided for bedroom circuit, 406.8(B) weatherproof in-use cover shall be provided outdoors
ELE07-00886 Electrical Rough-In3/19/20073/20/20073/20/2007 8:09:29 AMAPASS
Phone #: ###-#### front parapet ok to cover