ELE07-00888
| Electrical Rough-In | 3/20/2007 | 3/20/2007 | 3/20/2007 3:16:58 PM | P | PASS |
|
|
Phone #: ###-#### corr made, ric ok
|
ELE07-00878
| Temporary Service | 3/20/2007 | 3/20/2007 | 3/20/2007 2:34:22 PM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 3/20/2007 at 10:28:37 AM. Contact: ###-####. called contr, left corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection, 110.12(C) there shall be no broken parts-50a recpt, there shall be no contamination-inside panel, there shall be no damaged parts-gec, BCC job id sticker shall be posted
|
ELE07-00312
| Final | 3/20/2007 | 3/20/2007 | 3/20/2007 1:53:17 PM | P | PASS |
|
|
paul; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok to final, signed occ card
|
ELE07-00185
| Final | 3/20/2007 | 3/20/2007 | 3/20/2007 1:05:35 PM | P | FAIL |
|
|
ready for final, please contact Patrick, thank you Phone #: ###-#### called contr, left corr notice, nec 352.30(A) rnc shall be strapped within 3' of termination, 408.4 & 110.22 circuit directory shall be clear concise and specific to its purpose, 110.26(A) work space shall be provided about inside and outside panels as code states, BCC job shall be completed with all devices installed- rear outlet
|
ELE06-01263
| Final | 3/20/2007 | 3/20/2007 | 3/20/2007 12:19:50 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 3/20/2007 at 7:16:45 AM. Contact: ###-####. called contr to chg stranded to solid #8 to bond motors, ok to final
|
ELE07-00185
| Electrical Rough-In | 3/20/2007 | 3/20/2007 | 3/20/2007 11:20:12 AM | P | CANC |
|
|
Please contact Miles, thank you Phone #: ###-#### Inspection cancelled from web by: Wendy Waters
|
ELE07-00901
| Conference | 3/19/2007 | 3/20/2007 | 3/20/2007 10:36:05 AM | A | DONE |
|
|
please call 30 mintues prior so we can meet you out there. Phone #: ###-#### reviewed relocating each apt panel and looked at service feeders in basement areas, said no violations shall be retained and to be sure 4-wire to ranges
|
ELE07-00903
| Electrical Rough-In | 3/19/2007 | 3/20/2007 | 3/20/2007 9:40:39 AM | A | PASS |
|
|
jessie; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ri ok, see final
|
ELE07-00903
| Final | 3/20/2007 | 3/20/2007 | 3/20/2007 9:40:10 AM | A | PASS |
|
|
jessie; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok to final
|
ELE05-01204
| Final | 3/19/2007 | 3/20/2007 | 3/20/2007 9:11:35 AM | A | FAIL |
|
|
Mike; Phone #: ###-#### Internet Inspection Request from: Stacie Backus met owner, left corr notice, nec 210.8(A) (6) & (2) & (3) kitchen and garage and outside receptacles shall be gfci protected, 408.4 circuit directory shall be clear, concise, and complete for each circuit, 422.31(B) water heater and furnace shall have disconnects, 110.3(B) equipment shall be installed per listing and labelling- no open grounds or reverse polarity, 210.12 arc fault protection shall be provided for bedroom circuit, 406.8(B) weatherproof in-use cover shall be provided outdoors
|
ELE07-00886
| Electrical Rough-In | 3/19/2007 | 3/20/2007 | 3/20/2007 8:09:29 AM | A | PASS |
|
|
Phone #: ###-#### front parapet ok to cover
|