Inspections for the day of: Tuesday, March 20, 2007.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00800 INSP-Sprinkler Rough-in3/19/20073/20/20073/21/2007 9:18:43 AMPDEFR
Inspection rescheduled.
FIR07-00064 INSP-Final Inspection3/19/20073/20/20073/20/2007 3:53:45 PMPNH
No access.
FIR07-00174 INSP-Sprinkler Rough-in3/19/20073/20/20073/20/2007 3:27:10 PMAPART
OH fire sprinkler install is approved for cover, all field modifications to be indicated on as-built plans.
FIR06-00609 INSP-Final Inspection3/19/20073/20/20073/20/2007 3:25:22 PMAPASS
Fire alarm permit finaled, inspection passed.
BLD07-00166 FIRE-Final Inspection3/19/20073/20/20073/20/2007 2:02:58 PMAPASS
Fire life safety inspection passed, noted two items 1) the provided PFE's to be tagged with a current certification as the annual inspection is now due, 2) manual thumbturn locks at the two existing exit doors to be removed, these two items to be completed prior to structural final as discussed.
FIR07-00189 INSP-Final Inspection3/20/20073/20/20073/20/2007 1:09:14 PMPPASS
Fire alarm permit finaled.
FIR07-00189 INSP-Sprinkler Rough-in/Hydro3/19/20073/20/20073/20/2007 1:08:40 PMAPASS
Inspection request is for FA, not FP as indicated, inspeciton completed and work passed.
FIR06-00136 INSP-Final Inspection3/19/20073/20/20073/20/2007 1:04:49 PMAPASS
Fire alarm work passed inspection, permit finaled.
FIR05-00612 INSP-Final Inspection3/19/20073/20/20073/20/2007 1:03:53 PMAPASS
Corrections verified, fire alarm passed inspeciton, permit finaled.
BLD06-03461 FIRE-Final Inspection3/19/20073/20/20073/20/2007 10:48:28 AMAFAIL
Need to provide a current annual inspection for the existing fire sprinkler system, provide protection for the spray booth per review notes, missing one PFE for the office area, provide approved door hardware at one restroom in the office, repair exit discharge light at one location, provide combo exit sign and emergency light at the SW warehouse exit door, remove door knob at passage door to one marked exit, blank wires and provide a cover for one open junction box as marked on plans.