FIR06-00800
| INSP-Sprinkler Rough-in | 3/19/2007 | 3/20/2007 | 3/21/2007 9:18:43 AM | P | DEFR |
|
|
Inspection rescheduled.
|
FIR07-00064
| INSP-Final Inspection | 3/19/2007 | 3/20/2007 | 3/20/2007 3:53:45 PM | P | NH |
|
|
No access.
|
FIR07-00174
| INSP-Sprinkler Rough-in | 3/19/2007 | 3/20/2007 | 3/20/2007 3:27:10 PM | A | PART |
|
|
OH fire sprinkler install is approved for cover, all field modifications to be indicated on as-built plans.
|
FIR06-00609
| INSP-Final Inspection | 3/19/2007 | 3/20/2007 | 3/20/2007 3:25:22 PM | A | PASS |
|
|
Fire alarm permit finaled, inspection passed.
|
BLD07-00166
| FIRE-Final Inspection | 3/19/2007 | 3/20/2007 | 3/20/2007 2:02:58 PM | A | PASS |
|
|
Fire life safety inspection passed, noted two items 1) the provided PFE's to be tagged with a current certification as the annual inspection is now due, 2) manual thumbturn locks at the two existing exit doors to be removed, these two items to be completed prior to structural final as discussed.
|
FIR07-00189
| INSP-Final Inspection | 3/20/2007 | 3/20/2007 | 3/20/2007 1:09:14 PM | P | PASS |
|
|
Fire alarm permit finaled.
|
FIR07-00189
| INSP-Sprinkler Rough-in/Hydro | 3/19/2007 | 3/20/2007 | 3/20/2007 1:08:40 PM | A | PASS |
|
|
Inspection request is for FA, not FP as indicated, inspeciton completed and work passed.
|
FIR06-00136
| INSP-Final Inspection | 3/19/2007 | 3/20/2007 | 3/20/2007 1:04:49 PM | A | PASS |
|
|
Fire alarm work passed inspection, permit finaled.
|
FIR05-00612
| INSP-Final Inspection | 3/19/2007 | 3/20/2007 | 3/20/2007 1:03:53 PM | A | PASS |
|
|
Corrections verified, fire alarm passed inspeciton, permit finaled.
|
BLD06-03461
| FIRE-Final Inspection | 3/19/2007 | 3/20/2007 | 3/20/2007 10:48:28 AM | A | FAIL |
|
|
Need to provide a current annual inspection for the existing fire sprinkler system, provide protection for the spray booth per review notes, missing one PFE for the office area, provide approved door hardware at one restroom in the office, repair exit discharge light at one location, provide combo exit sign and emergency light at the SW warehouse exit door, remove door knob at passage door to one marked exit, blank wires and provide a cover for one open junction box as marked on plans.
|