FIR06-00434
| FIR-Aging Inspection | 3/20/2008 | 3/20/2008 | 3/24/2008 5:11:12 PM | P | DONE |
|
|
Ready for final.
|
FIR06-00238
| FIR-Aging Inspection | 3/20/2008 | 3/20/2008 | 3/21/2008 4:41:29 PM | P | DONE |
|
|
Permit ready for final.
|
FIR08-00106
| INSP-Final Inspection | 3/20/2008 | 3/20/2008 | 3/21/2008 4:33:06 PM | P | PART |
|
|
Final pending relocation of one pendent head to avoid exceeding min. separation or the installation of a baffle as discussed.
|
FIR06-00449
| INSP-Final Inspection | 3/20/2008 | 3/20/2008 | 3/20/2008 4:35:24 PM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
FIR06-00449
| FIR-Aging Inspection | 3/20/2008 | 3/20/2008 | 3/20/2008 3:21:30 PM | P | DONE |
|
|
Permit work completed, doc final pending.
|
BLD07-03175
| FIRE-Final Inspection | 3/19/2008 | 3/20/2008 | 3/20/2008 3:13:01 PM | P | NR |
|
|
Missing doors and hardware at some locations, need verification that HVAC units are below 2000 cfm as duct detectors are not installed, remainder of life safety is satisfactory.
|
FIR08-00080
| INSP-Final Inspection | 3/19/2008 | 3/20/2008 | 3/20/2008 3:10:10 PM | P | PASS |
|
|
Fire sprinkler permit work passed final inspection, permit finaled.
|
FIR08-00156
| INSP-Final Inspection | 3/19/2008 | 3/20/2008 | 3/20/2008 3:09:14 PM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
FIR08-00165
| INSP-Sprinkler Rough-in | 3/20/2008 | 3/20/2008 | 3/20/2008 2:07:49 PM | P | DEFR |
|
|
Inspection rescheduled.
|
FIR07-00827
| INSP-Sprinkler Rough-in | 3/19/2008 | 3/20/2008 | 3/20/2008 2:06:13 PM | A | PART |
|
|
Okayed for ceiling cover at areas as circled and marked with today's date on stamped plan set.
|
FIR07-00437
| INSP-Sprinkler Rough-in | 3/19/2008 | 3/20/2008 | 3/20/2008 2:05:12 PM | A | PART |
|
|
OH work is approved for cover at the corridor and nurses station as marked on plans, noted one deleted head no longer required, one head at a janitors closet to be replaced due to deflector damage-see annotation on drawings.
|
FIR07-00860
| INSP-Final Inspection | 3/19/2008 | 3/20/2008 | 3/20/2008 2:01:53 PM | A | PASS |
|
|
Fire sprinkler permit finaled.
|
FIR07-00935
| FIR-Aging Inspection | 3/20/2008 | 3/20/2008 | 3/20/2008 12:54:09 PM | | DEFR |
|
|
Work in progress, construction underway.
|
FIR08-00048
| INSP-Sprinkler Rough-in | 3/20/2008 | 3/20/2008 | 3/20/2008 12:52:40 PM | P | PART |
|
|
Fire sprinkler work at the hard lid ceilings is approved for cover.
|
FIR08-00113
| INSP-Sprinkler Rough-in | 3/19/2008 | 3/20/2008 | 3/20/2008 12:51:28 PM | A | PART |
|
|
Overhead fire sprinkler rough-in is approved for cover at the drop ceilings as noted on plans.
|
FIR07-00965
| INSP-Final Inspection | 3/20/2008 | 3/20/2008 | 3/20/2008 11:37:16 AM | P | PASS |
|
|
Fire alarm permit finaled.
|
FIR07-00965
| INSP-Alarm Testing | 3/18/2008 | 3/20/2008 | 3/20/2008 11:36:38 AM | A | PASS |
|
|
Fire alarm field testing completed acceptable, permit finaled.
|
FIR07-00964
| INSP-Final Inspection | 3/18/2008 | 3/20/2008 | 3/20/2008 11:34:25 AM | A | PASS |
|
|
Fire sprinkler work completed satisfactory, inspection passed, permit finaled.
|
FIR07-00710
| INSP-Final Inspection | 3/19/2008 | 3/20/2008 | 3/20/2008 9:52:49 AM | A | PASS |
|
|
Corrections are complete, will verify plastic at unit smoke alarms is removed prior to building permit final. Fire alarm permit finaled.
|