Inspections for the day of: Thursday, March 20, 2008.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00434 FIR-Aging Inspection3/20/20083/20/20083/24/2008 5:11:12 PMPDONE
Ready for final.
FIR06-00238 FIR-Aging Inspection3/20/20083/20/20083/21/2008 4:41:29 PMPDONE
Permit ready for final.
FIR08-00106 INSP-Final Inspection3/20/20083/20/20083/21/2008 4:33:06 PMPPART
Final pending relocation of one pendent head to avoid exceeding min. separation or the installation of a baffle as discussed.
FIR06-00449 INSP-Final Inspection3/20/20083/20/20083/20/2008 4:35:24 PMPPASS
Fire sprinkler permit finaled.
FIR06-00449 FIR-Aging Inspection3/20/20083/20/20083/20/2008 3:21:30 PMPDONE
Permit work completed, doc final pending.
BLD07-03175 FIRE-Final Inspection3/19/20083/20/20083/20/2008 3:13:01 PMPNR
Missing doors and hardware at some locations, need verification that HVAC units are below 2000 cfm as duct detectors are not installed, remainder of life safety is satisfactory.
FIR08-00080 INSP-Final Inspection3/19/20083/20/20083/20/2008 3:10:10 PMPPASS
Fire sprinkler permit work passed final inspection, permit finaled.
FIR08-00156 INSP-Final Inspection3/19/20083/20/20083/20/2008 3:09:14 PMPPASS
Fire sprinkler permit finaled.
FIR08-00165 INSP-Sprinkler Rough-in3/20/20083/20/20083/20/2008 2:07:49 PMPDEFR
Inspection rescheduled.
FIR07-00827 INSP-Sprinkler Rough-in3/19/20083/20/20083/20/2008 2:06:13 PMAPART
Okayed for ceiling cover at areas as circled and marked with today's date on stamped plan set.
FIR07-00437 INSP-Sprinkler Rough-in3/19/20083/20/20083/20/2008 2:05:12 PMAPART
OH work is approved for cover at the corridor and nurses station as marked on plans, noted one deleted head no longer required, one head at a janitors closet to be replaced due to deflector damage-see annotation on drawings.
FIR07-00860 INSP-Final Inspection3/19/20083/20/20083/20/2008 2:01:53 PMAPASS
Fire sprinkler permit finaled.
FIR07-00935 FIR-Aging Inspection3/20/20083/20/20083/20/2008 12:54:09 PM DEFR
Work in progress, construction underway.
FIR08-00048 INSP-Sprinkler Rough-in3/20/20083/20/20083/20/2008 12:52:40 PMPPART
Fire sprinkler work at the hard lid ceilings is approved for cover.
FIR08-00113 INSP-Sprinkler Rough-in3/19/20083/20/20083/20/2008 12:51:28 PMAPART
Overhead fire sprinkler rough-in is approved for cover at the drop ceilings as noted on plans.
FIR07-00965 INSP-Final Inspection3/20/20083/20/20083/20/2008 11:37:16 AMPPASS
Fire alarm permit finaled.
FIR07-00965 INSP-Alarm Testing3/18/20083/20/20083/20/2008 11:36:38 AMAPASS
Fire alarm field testing completed acceptable, permit finaled.
FIR07-00964 INSP-Final Inspection3/18/20083/20/20083/20/2008 11:34:25 AMAPASS
Fire sprinkler work completed satisfactory, inspection passed, permit finaled.
FIR07-00710 INSP-Final Inspection3/19/20083/20/20083/20/2008 9:52:49 AMAPASS
Corrections are complete, will verify plastic at unit smoke alarms is removed prior to building permit final. Fire alarm permit finaled.