Inspections for the day of: Friday, March 20, 2009.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00018 INSP-Sprinkler Rough-in/Hydro3/16/20093/20/20093/23/2009 8:28:27 AMPPART
See inspection comments per T. Frost.
FIR09-00127 INSP-Sprinkler Rough-in3/20/20093/20/20093/20/2009 4:53:50 PMPFAIL
See inspection comments per T. Frost.
FIR07-01051 INSP-Sprinkler Rough-in3/19/20093/20/20093/20/2009 4:53:00 PMPPART
See plans marked with today's date for corridors and classrooms on the first and second floors inspected and okayed for cover, noted one overspaced head, discussed dry pendent locations at the coolers.
FIR08-00270 INSP-Sprinkler Rough-in/Hydro3/20/20093/20/20093/20/2009 3:51:51 PMPFAIL
Hydrostatic testing failed due to visible leakage at hose valve connections and pressure loss at the guages.
FIR09-00159 INSP-Sprinkler Rough-in/Hydro3/19/20093/20/20093/20/2009 3:49:01 PMAFAIL
UG supply line hydrostatic test failed due to pressure loss at the guage per inspection by T. Frost.
FIR09-00160 INSP-Sprinkler Rough-in/Hydro3/19/20093/20/20093/20/2009 3:47:26 PMAPART
UG fire supply line hydrostatic test passed per T. Frost.
FIR08-00103 INSP-Final Inspection3/19/20093/20/20093/20/2009 3:45:29 PMAPASS
Fire alarm permit approved for final.
BLD08-02248 FIRE-Final Inspection3/19/20093/20/20093/20/2009 2:03:10 PMAPASS
Correction list items field verified for completion, project related FIR permits finaled, additional fire extinguisher at the new sales floor area to be posted as discussed, life safety passed.
FIR09-00170 INSP-Final Inspection3/20/20093/20/20093/20/2009 2:00:40 PMPPASS
Scope of fire alarm quick permit work passed inspection, permit finaled.
FIR08-00270 INSP-Sprinkler Rough-in/Hydro3/19/20093/20/20093/20/2009 11:58:33 AMAPART
Flow testing at remote hose stations per system design completed satisfactory in conjunction with fire dept. apparatus at the street side FDC.
FIR08-00863 INSP-Final Inspection3/19/20093/20/20093/20/2009 11:43:15 AMAPART
Final pending project related fire alarm work for riser supervision. Discussed additonal items for final including backflow cert., calc. sticker, tags, outside bell test, final walkthrough, etc.
FIR09-00152 INSP-Final Inspection3/19/20093/20/20093/20/2009 11:40:24 AMANR
Work is not ready for final inspection per phone call from alarm contractor (Matt ###-####).
BLD09-00249 FIRE-Final Inspection3/19/20093/20/20093/20/2009 11:38:27 AMAFAIL
EM light at the east wall is not functional, provide a current certification tag for the existing fire extinguisher, install approved hardware at the second exit or remove signage.
FIR08-00820 FIR-Aging Inspection3/20/20093/20/20093/20/2009 9:36:40 AM PEND
Need site inspection request for permit final.
FIR09-00027 INSP-Sprinkler Rough-in/Hydro3/19/20093/20/20093/20/2009 9:35:31 AMAFAIL
Thrust block at the 45 deg ell is not satisfactory, noted one section of piping needs properly bedded, remiander of installation is okay for cover-see plans for locations approved for bury.