FIR08-00018
| INSP-Sprinkler Rough-in/Hydro | 3/16/2009 | 3/20/2009 | 3/23/2009 8:28:27 AM | P | PART |
|
|
See inspection comments per T. Frost.
|
FIR09-00127
| INSP-Sprinkler Rough-in | 3/20/2009 | 3/20/2009 | 3/20/2009 4:53:50 PM | P | FAIL |
|
|
See inspection comments per T. Frost.
|
FIR07-01051
| INSP-Sprinkler Rough-in | 3/19/2009 | 3/20/2009 | 3/20/2009 4:53:00 PM | P | PART |
|
|
See plans marked with today's date for corridors and classrooms on the first and second floors inspected and okayed for cover, noted one overspaced head, discussed dry pendent locations at the coolers.
|
FIR08-00270
| INSP-Sprinkler Rough-in/Hydro | 3/20/2009 | 3/20/2009 | 3/20/2009 3:51:51 PM | P | FAIL |
|
|
Hydrostatic testing failed due to visible leakage at hose valve connections and pressure loss at the guages.
|
FIR09-00159
| INSP-Sprinkler Rough-in/Hydro | 3/19/2009 | 3/20/2009 | 3/20/2009 3:49:01 PM | A | FAIL |
|
|
UG supply line hydrostatic test failed due to pressure loss at the guage per inspection by T. Frost.
|
FIR09-00160
| INSP-Sprinkler Rough-in/Hydro | 3/19/2009 | 3/20/2009 | 3/20/2009 3:47:26 PM | A | PART |
|
|
UG fire supply line hydrostatic test passed per T. Frost.
|
FIR08-00103
| INSP-Final Inspection | 3/19/2009 | 3/20/2009 | 3/20/2009 3:45:29 PM | A | PASS |
|
|
Fire alarm permit approved for final.
|
BLD08-02248
| FIRE-Final Inspection | 3/19/2009 | 3/20/2009 | 3/20/2009 2:03:10 PM | A | PASS |
|
|
Correction list items field verified for completion, project related FIR permits finaled, additional fire extinguisher at the new sales floor area to be posted as discussed, life safety passed.
|
FIR09-00170
| INSP-Final Inspection | 3/20/2009 | 3/20/2009 | 3/20/2009 2:00:40 PM | P | PASS |
|
|
Scope of fire alarm quick permit work passed inspection, permit finaled.
|
FIR08-00270
| INSP-Sprinkler Rough-in/Hydro | 3/19/2009 | 3/20/2009 | 3/20/2009 11:58:33 AM | A | PART |
|
|
Flow testing at remote hose stations per system design completed satisfactory in conjunction with fire dept. apparatus at the street side FDC.
|
FIR08-00863
| INSP-Final Inspection | 3/19/2009 | 3/20/2009 | 3/20/2009 11:43:15 AM | A | PART |
|
|
Final pending project related fire alarm work for riser supervision. Discussed additonal items for final including backflow cert., calc. sticker, tags, outside bell test, final walkthrough, etc.
|
FIR09-00152
| INSP-Final Inspection | 3/19/2009 | 3/20/2009 | 3/20/2009 11:40:24 AM | A | NR |
|
|
Work is not ready for final inspection per phone call from alarm contractor (Matt ###-####).
|
BLD09-00249
| FIRE-Final Inspection | 3/19/2009 | 3/20/2009 | 3/20/2009 11:38:27 AM | A | FAIL |
|
|
EM light at the east wall is not functional, provide a current certification tag for the existing fire extinguisher, install approved hardware at the second exit or remove signage.
|
FIR08-00820
| FIR-Aging Inspection | 3/20/2009 | 3/20/2009 | 3/20/2009 9:36:40 AM | | PEND |
|
|
Need site inspection request for permit final.
|
FIR09-00027
| INSP-Sprinkler Rough-in/Hydro | 3/19/2009 | 3/20/2009 | 3/20/2009 9:35:31 AM | A | FAIL |
|
|
Thrust block at the 45 deg ell is not satisfactory, noted one section of piping needs properly bedded, remiander of installation is okay for cover-see plans for locations approved for bury.
|