ELE12-01801
| Final | 3/20/2014 | 3/20/2014 | 3/20/2014 2:16:10 PM | P | PASS |
|
|
ok final
|
ELE14-00664
| Temporary Service | 3/20/2014 | 3/20/2014 | 3/20/2014 2:03:44 PM | P | PASS |
|
|
Temp Pole Phone #: ###-#### >> Inspection requested via web by Rowdy Monroe t/s u/g n ok
|
ELE13-01878
| Final | 3/20/2014 | 3/20/2014 | 3/20/2014 12:55:02 PM | P | FAIL |
|
|
Darren Phone #: ###-#### called, corrections not all made, shall strap mc cable within 12" of fixtures where branch circuit, see NEC 330(30)(B) shall strap flex at heater, see NEC 348.30(A), shall provide gfci for washer within 6' of sink, see NEC 210.8(B)(5)
|
ELE12-01158
| Final | 3/20/2014 | 3/20/2014 | 3/20/2014 11:45:13 AM | P | PASS |
|
|
ok final
|
ELE12-00109
| Final | 3/19/2014 | 3/20/2014 | 3/20/2014 10:26:01 AM | A | PASS |
|
|
go in by side gate, garage door is unlocked, panel is in garage. (House is currently for sale and unoccupied) Phone #: ###-#### >> Inspection requested via web by Louis Keller corrections made, ok final
|
ELE14-00482
| Electrical Rough-In | 3/20/2014 | 3/20/2014 | 3/20/2014 10:11:28 AM | A | PASS |
|
|
call first ###-#### Phone #: ###-#### >> Inspection requested via web by PAT MILLER ri ok
|
ELE14-00660
| Temporary Service | 3/19/2014 | 3/20/2014 | 3/20/2014 9:37:47 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Bob Glenn t/s u/g n ok
|
ELE14-00659
| Temporary Service | 3/19/2014 | 3/20/2014 | 3/20/2014 9:24:08 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Bob Glenn t/s u/g n ok
|
ELE14-00658
| Temporary Service | 3/19/2014 | 3/20/2014 | 3/20/2014 8:47:17 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Bob Glenn t/s u/g n ok
|
ELE14-00662
| Electrical Rough-In | 3/19/2014 | 3/20/2014 | 3/20/2014 8:21:24 AM | A | PASS |
|
|
Swimming pool bonding: - (2) autocover - (1) equipment - (1) fence Phone #: ###-#### >> Inspection requested via web by Lars Johnson pool bonding for items listed ok
|