ELE14-01819
| Electrical Rough-In | 3/20/2015 | 3/20/2015 | 3/20/2015 2:46:50 PM | P | PASS |
|
|
Contact: Jeremy Thornock, underground inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden r/i ok conduits for light poles
|
ELE15-00285
| Electrical Rough-In | 3/19/2015 | 3/20/2015 | 3/20/2015 2:18:23 PM | P | PASS |
|
|
Robert. Phone #: ###-#### Inspection requested via web by Sean DeLacy r/i ceilings ok
|
ELE15-00124
| Final | 3/19/2015 | 3/20/2015 | 3/20/2015 1:48:01 PM | P | PASS |
|
|
15th // Jose Phone #: ###-#### final ok 15th flr
|
ELE14-02739
| Electrical Rough-In | 3/17/2015 | 3/20/2015 | 3/20/2015 1:07:39 PM | P | FAIL |
|
|
Jerome Phone #: ###-#### 334.30-nm cable shall be supported and secured by stapling within 12" of box and every 41/2 feet. 300.4- (A)(1)-where a cable is ran thru bored holes, not less than 11/4" from hole to edge of stud. Nailpales required to fix problem. Make up ground wires prior to inspection. Use colorado jims or stackers for firred out walls to support nm cable.
|
ELE13-01291
| Electrical Rough-In | 3/19/2015 | 3/20/2015 | 3/20/2015 10:22:15 AM | A | PASS |
|
|
Contact Brandon Robinson for 4th level east side rough in. Phone #: ###-#### Inspection requested via web by Tom Betty r/i 4th level est side tractor box ceiling and walls ok
|
ELE15-00506
| Electrical Rough-In | 3/19/2015 | 3/20/2015 | 3/20/2015 9:55:03 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by JENNY EMEL r/i ceilings ok all areas
|
ELE15-00667
| Electrical Rough-In | 3/18/2015 | 3/20/2015 | 3/20/2015 9:21:08 AM | A | PASS |
|
|
Wall Cover. Von is the onsite contact Phone #: ###-#### Inspection requested via web by Buster Bowen r/i walls ok
|
ELE15-00722
| Final | 3/20/2015 | 3/20/2015 | 3/20/2015 8:51:12 AM | P | PASS |
|
|
Tom Phone #: ###-#### power to IT dept. exhaust fan final ok
|
ELE14-01182
| Electrical Rough-In | 3/19/2015 | 3/20/2015 | 3/20/2015 8:48:56 AM | A | PASS |
|
|
Ceiling inspection. Shane is the contact his cell no. is ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates r/i print shop ceilings ok
|
ELE15-02132
| Electrical Rough-In | 3/20/2015 | 3/20/2015 | 3/20/2015 12:00:00 AM | A | PASS |
|
|
Rough-in west wing units. Phone #: ###-#### Inspection requested via web by Rafael Castillo r/i ok 2nd floor west wing rooms
|