BLD14-02817
| FIRE-Conference | 3/20/2015 | 3/20/2015 | 3/31/2015 12:03:10 PM | P | DONE |
|
|
Project related fire sprinkler permit work finaled. Need to repair door closure at the brewery room west side. Informed tenant to provide a permanent power source to attic fans above the kitchen coolers- extension cords not allowed.
|
FIR14-00778
| INSP-Sprinkler Rough-in | 3/19/2015 | 3/20/2015 | 3/20/2015 7:12:11 PM | A | FAIL |
|
|
Area G dry system install does not correlate with approved plan set regarding main routing.
|
FIR14-00708
| INSP-Sprinkler Rough-in | 3/19/2015 | 3/20/2015 | 3/20/2015 7:09:23 PM | A | PART |
|
|
Overhead inspection for the 3rd floor area G wet system at living units only, including tenting, okayed per as-built plans matching install with the exception of two balconies now covered by dry system.
|
FIR14-00815
| INSP-Sprinkler Rough-in | 3/19/2015 | 3/20/2015 | 3/20/2015 3:30:47 PM | A | PART |
|
|
Rough-in inspection at living units 2nd floor area 3- sheets FP11 and FP9 completed. Need to relocate one blocked sprinkler at unit 227. Remainder okayed, refer to dated annotations.
|
FIR14-00783
| INSP-Sprinkler Rough-in | 3/19/2015 | 3/20/2015 | 3/20/2015 3:28:09 PM | A | PART |
|
|
Inspection for thrust blocking completed satisfactory- okay to cover at areas installed to date.
|
FIR14-00712
| INSP-Final Inspection | 3/20/2015 | 3/20/2015 | 3/20/2015 3:25:39 PM | P | PASS |
|
|
UG fire supply line flush and final completed. Permit final approved.
|
FIR15-00068
| INSP-Final Inspection | 3/18/2015 | 3/20/2015 | 3/20/2015 11:52:49 AM | A | PART |
|
|
Completed inspection of the new system addition per approved plans. Items noted include; missing seismic brace, spacing at uprights above the kitchen coolers needs adjustment, missing door closure at the west side of the brewery to meet conditions necessary for use of the room design method as indicated, existing system riser is overdue annual inspection.
|
FIR15-00162
| INSP-Final Inspection | 3/19/2015 | 3/20/2015 | 3/20/2015 11:45:11 AM | A | PASS |
|
|
Scope of work completed. Inspection passed, permit finaled.
|
FIR14-00876
| INSP-Final Inspection | 3/18/2015 | 3/20/2015 | 3/20/2015 11:43:52 AM | A | PASS |
|
|
UG fire supply line flush completed. Overhead system charged and flow tested. Verified dry upright at the attic, final walkthrough finished. Permit finaled.
|