Inspections for the day of: Tuesday, March 20, 2018.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-01028 Electrical Rough-In3/20/20183/20/20183/20/2018 1:48:38 PMPPASS
Point of contact is Luke at number listed above.
Wall rough-in inspection Phone #: ###-#### Inspection requested via web by Kevin Perez
1 conference room with floor receptacle in place and 5 receptacles minimum required also in place. Wall rough in ok cover
ELE18-00114 Final3/19/20183/20/20183/20/2018 11:01:01 AMAPASS
Phone #: ###-#### Inspection requested via web by Ryan Wake Final ok
ELE18-00987 Rough-In Permanent Service3/19/20183/20/20183/20/2018 10:12:41 AMAFAIL
Phone #: ###-#### Inspection requested via web by Zane Robertson
110.3- Power to chime transformer missed. 250.24(A)(5)- Grounded conductor shall not be connected to ground on the loadside of service disconnecting means. Remove grounding electrode conductor from sub panel.
314.17(A)- Open KO in entry 3/0 box. Shall close KO with approved means.
314.25- All boxes shall have covers. Recessed can in powder bath missing junction box cover.
ELE17-01337 Electrical Rough-In3/19/20183/20/20183/20/2018 9:16:28 AMAPASS
We are requesting a wall rough-in inspection in meeting room interior walls for tomorrow morning. Our contact is Rick @ ###-####. Thank you, Phone #: ###-#### Inspection requested via web by Clint Tate
Walls noted rough in ok cover