Inspections for the day of: Wednesday, March 20, 2019.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-00542 Final3/20/20193/20/20193/20/2019 2:49:33 PMPPASS
Contact: Rob Lawrence... Project cancelled as per customer Phone #: ###-#### Inspection requested via web by Deb Gooden
No work performed just conference on replacement. Costs skyrocketed due possible hazardous location.
ELE19-00970 Electrical Rough-In3/20/20193/20/20193/20/2019 2:29:09 PMPFAIL
Danny. Wall cover. Phone #: ###-#### Inspection requested via web by Sean DeLacy
110.3- Provide documentation on terminating MC with secondary equipment grounding conductor. All have been cut off.
300.4- Where MC is run through holes that do not maintain 1 1/4" from framing surface they shall be protected from physical damage. All shallow studs west and south sides.
ELE19-00934 Electrical Rough-In3/20/20193/20/20193/20/2019 1:20:57 PMPPASS
Phone #: ###-#### Inspection requested via web by Steven Ragan
Wall rough in ok cover
ELE19-00415 Final3/20/20193/20/20193/20/2019 1:03:56 PMPPART
We Are Ready For Final Please Cal Me I Am Home Sick Today But I Need To Talk To You! Phone #: ###-#### Inspection requested via web by jason shifflett

110.3- 3 receptacles not working, 2 in left office and 1 in right office,

110.22- Disconnecting means shall be labelled as which space it feeds.

314.25- All boxes with wiring shall have covers. 2 light boxes in ceiling near panel are open.
Listings of drivers and wiring photos OK.

All safed off. Temp line signed. TCO ok
ELE19-00958 Final3/19/20193/20/20193/20/2019 12:10:38 PMAPASS
Phone #: ###-#### Inspection requested via web by Kevin Perez Final ok
ELE19-00958 Electrical Rough-In3/20/20193/20/20193/20/2019 12:09:32 PMPPASS
Phone #: ###-#### Inspection requested via web by Kevin Perez
Exhaust fan added to down stairs nail salon rough in ok
ELE18-04555 Electrical Rough-In3/20/20193/20/20193/20/2019 11:53:18 AMPPASS
Underground for spare pipe fed from crane enclosure Phone #: ###-#### Inspection requested via web by Mike McCarrel
Area noted rough in ok cover
ELE18-04785 Electrical Rough-In3/20/20193/20/20193/20/2019 11:51:57 AMPPASS
Phone #: ###-#### Inspection requested via web by Tom Jenkins
maintainance building rough in ok cover
ELE19-00430 Electrical Rough-In3/19/20193/20/20193/20/2019 11:31:15 AMAPASS
Underground @ Nyala exhibit Phone #: ###-#### Inspection requested via web by Mike McCarrel Rough in noted rough in ok cover
ELE19-00949 Electrical Rough-In3/19/20193/20/20193/20/2019 10:43:27 AMAPASS
Underground in C-Store Phone #: ###-#### Inspection requested via web by Stan Woodward Under slab rough in ok cover
ELE19-00142 Final3/19/20193/20/20193/20/2019 10:30:55 AMAFAIL
garage code 2018 Phone #: ###-#### Inspection requested via web by Darryn Coburn
As per NEC 80.19(H) and BCC 4-05-26 inspector shall have access to all outlets installed for testing. Garage full of materials covering receptacles. Unable to test all. Rest of house checked OK.
ELE19-00955 Electrical Rough-In3/19/20193/20/20193/20/2019 9:47:49 AMAPASS
Ground work prior pouring slab - please contact Keith with any questions Phone #: ###-#### Inspection requested via web by JENNY EMEL
Underground to interior of cell enclosure from transformer and under slab rough in ok cover
ELE19-00943 Rough-In Permanent Service3/19/20193/20/20193/20/2019 9:25:05 AMAFAIL
Need service meter inspected for IPCO hookup. There is a strap missing on the 2'''' riser conduit into meter, we will install one when we run the conduits up the sign support column call if there are any problems thanks. Phone #: ###-#### Inspection requested via web by robert feller
110.24- Available fault current shall be posted with value and date calculated prior to permanent service inspection.

408.36(D)- Plug in type over current devices that are back fed shall be secured in place by additional fasteners.
Disregard fastening overcurrent device, reference is for field installed devices not factory installed.