ELE18-00542
| Final | 3/20/2019 | 3/20/2019 | 3/20/2019 2:49:33 PM | P | PASS |
|
|
Contact: Rob Lawrence... Project cancelled as per customer Phone #: ###-#### Inspection requested via web by Deb Gooden No work performed just conference on replacement. Costs skyrocketed due possible hazardous location.
|
ELE19-00970
| Electrical Rough-In | 3/20/2019 | 3/20/2019 | 3/20/2019 2:29:09 PM | P | FAIL |
|
|
Danny. Wall cover. Phone #: ###-#### Inspection requested via web by Sean DeLacy 110.3- Provide documentation on terminating MC with secondary equipment grounding conductor. All have been cut off. 300.4- Where MC is run through holes that do not maintain 1 1/4" from framing surface they shall be protected from physical damage. All shallow studs west and south sides.
|
ELE19-00934
| Electrical Rough-In | 3/20/2019 | 3/20/2019 | 3/20/2019 1:20:57 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Steven Ragan Wall rough in ok cover
|
ELE19-00415
| Final | 3/20/2019 | 3/20/2019 | 3/20/2019 1:03:56 PM | P | PART |
|
|
We Are Ready For Final Please Cal Me I Am Home Sick Today But I Need To Talk To You! Phone #: ###-#### Inspection requested via web by jason shifflett
110.3- 3 receptacles not working, 2 in left office and 1 in right office,
110.22- Disconnecting means shall be labelled as which space it feeds.
314.25- All boxes with wiring shall have covers. 2 light boxes in ceiling near panel are open. Listings of drivers and wiring photos OK.
All safed off. Temp line signed. TCO ok
|
ELE19-00958
| Final | 3/19/2019 | 3/20/2019 | 3/20/2019 12:10:38 PM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kevin Perez Final ok
|
ELE19-00958
| Electrical Rough-In | 3/20/2019 | 3/20/2019 | 3/20/2019 12:09:32 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kevin Perez Exhaust fan added to down stairs nail salon rough in ok
|
ELE18-04555
| Electrical Rough-In | 3/20/2019 | 3/20/2019 | 3/20/2019 11:53:18 AM | P | PASS |
|
|
Underground for spare pipe fed from crane enclosure Phone #: ###-#### Inspection requested via web by Mike McCarrel Area noted rough in ok cover
|
ELE18-04785
| Electrical Rough-In | 3/20/2019 | 3/20/2019 | 3/20/2019 11:51:57 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Tom Jenkins maintainance building rough in ok cover
|
ELE19-00430
| Electrical Rough-In | 3/19/2019 | 3/20/2019 | 3/20/2019 11:31:15 AM | A | PASS |
|
|
Underground @ Nyala exhibit Phone #: ###-#### Inspection requested via web by Mike McCarrel Rough in noted rough in ok cover
|
ELE19-00949
| Electrical Rough-In | 3/19/2019 | 3/20/2019 | 3/20/2019 10:43:27 AM | A | PASS |
|
|
Underground in C-Store Phone #: ###-#### Inspection requested via web by Stan Woodward Under slab rough in ok cover
|
ELE19-00142
| Final | 3/19/2019 | 3/20/2019 | 3/20/2019 10:30:55 AM | A | FAIL |
|
|
garage code 2018 Phone #: ###-#### Inspection requested via web by Darryn Coburn As per NEC 80.19(H) and BCC 4-05-26 inspector shall have access to all outlets installed for testing. Garage full of materials covering receptacles. Unable to test all. Rest of house checked OK.
|
ELE19-00955
| Electrical Rough-In | 3/19/2019 | 3/20/2019 | 3/20/2019 9:47:49 AM | A | PASS |
|
|
Ground work prior pouring slab - please contact Keith with any questions Phone #: ###-#### Inspection requested via web by JENNY EMEL Underground to interior of cell enclosure from transformer and under slab rough in ok cover
|
ELE19-00943
| Rough-In Permanent Service | 3/19/2019 | 3/20/2019 | 3/20/2019 9:25:05 AM | A | FAIL |
|
|
Need service meter inspected for IPCO hookup. There is a strap missing on the 2'''' riser conduit into meter, we will install one when we run the conduits up the sign support column call if there are any problems thanks. Phone #: ###-#### Inspection requested via web by robert feller 110.24- Available fault current shall be posted with value and date calculated prior to permanent service inspection.
408.36(D)- Plug in type over current devices that are back fed shall be secured in place by additional fasteners. Disregard fastening overcurrent device, reference is for field installed devices not factory installed.
|