Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00238 INSP-Final Inspection3/21/20083/21/20083/21/2008 4:42:34 PMPPASS
UG fire supply line permit finaled.
FIR08-00182 INSP-Sprinkler Rough-in3/20/20083/21/20083/21/2008 4:35:15 PMPPART
UG fire supply line is acceptable for cover including the ductile riser stub.
FIR08-00102 INSP-Final Inspection3/20/20083/21/20083/21/2008 4:30:38 PMAPASS
Fire alarm testing passed inspection, permit finaled.
FIR07-00906 INSP-Final Inspection3/20/20083/21/20083/21/2008 2:10:03 PMPPASS
Fire alarm testing for this permit complete.KR
FIR08-00111 INSP-Final Inspection3/20/20083/21/20083/21/2008 2:08:41 PMPPASS
Fire alarm test complete. KR
FIR06-00540 INSP-Sprinkler Rough-in/Hydro3/18/20083/21/20083/21/2008 1:03:29 PMAPART
Inspection completed satisfactory for the seismic upgrade work at the plaza level mains, also inspected the remainder of 2" feed piping for the plaza level bridge lines. Hydrostatic testing for this portion of work passed.
FIR07-00958 FIR-Aging Inspection3/21/20083/21/20083/21/2008 11:41:34 AM DONE
Work in progress, construction underway. Activity pending site inspection request.
BLD07-03175 FIRE-Final Inspection3/21/20083/21/20083/21/2008 11:38:29 AMPPASS
HVAC units are below 2000 cfm per contractor and mechanical sheet, remainder of items completed, fire life safety inspection passed.
BLD06-03307 FIRE-Final Inspection3/20/20083/21/20083/21/2008 11:24:44 AMAPASS
Fire life safety passed inspection.
BLD07-01505 FIRE-Final Inspection3/20/20083/21/20083/21/2008 11:23:54 AMAPASS
Necessary corrections are complete per last C/N, fire life safety finaled.
FIR06-00365 INSP-Final Inspection3/20/20083/21/20083/21/2008 11:21:55 AMAFAIL
Missing ceilings at some locations, need missing escutcheons installed, noted sprinkler head adjacent to the elevator equipment panel must be located within 2' of the heat detector for shunt trip per state elevator requirements.
FIR07-00425 INSP-Final Inspection3/20/20083/21/20083/21/2008 11:15:35 AMAPASS
Items on the issued correction notice verified for compliance, fire sprinkler passed final field inspection, permit finaled. NOTE: see project related FIR permit # FIR07-00365 for some field inspection notes related to this permit.