FIR07-01033
| INSP-Final Inspection | 3/21/2008 | 3/21/2008 | 3/21/2008 4:25:45 PM | P | PASS |
|
|
Test the connection between hood system and fire alarm. Test complete. KR
|
FIR07-00934
| INSP-Final Inspection | 3/20/2008 | 3/21/2008 | 3/21/2008 4:23:12 PM | A | PASS |
|
|
Hood inspections complete.Repairs corrected per last inspection.KR
|
FIR07-00784
| INSP-Final Inspection | 3/21/2008 | 3/21/2008 | 3/21/2008 3:56:08 PM | P | PASS |
|
|
permit finaled
|
FIR08-00165
| INSP-Sprinkler Rough-in | 3/20/2008 | 3/21/2008 | 3/21/2008 2:44:35 PM | A | PART |
|
|
See the city approved plans for the open office area where the sprinkler piping is ok to cover.
|
FIR08-00171
| INSP-Alarm Testing | 3/20/2008 | 3/21/2008 | 3/21/2008 2:12:36 PM | A | PASS |
|
|
Fire alarm test complete per this permit.KR
|
FIR07-00578
| INSP-Final Inspection | 3/20/2008 | 3/21/2008 | 3/21/2008 12:39:56 PM | A | FAIL |
|
|
Just need to verify the fire proofing has been repaired to final. Forward flush passed.
|
FIR07-00841
| INSP-Final Inspection | 3/20/2008 | 3/21/2008 | 3/21/2008 12:26:11 PM | A | PASS |
|
|
permit finaled
|
FIR07-00697
| INSP-Sprinkler Rough-in/Hydro | 3/20/2008 | 3/21/2008 | 3/21/2008 12:25:05 PM | A | FAIL |
|
|
I found the sprinkler piping in the Daycare and the next two adjoining rooms sizing did not match plans. 1" piping was installed where 1 1/2" was shown. Also 1 1/2" piping was installed where 2" piping was shown. I went over these discrepancies with the fitter and also contacted Shilos office and spoke to Stan. I stopped the inspection after these three rooms. I let all of the involved parties know that the piping installed needs to match the plans or the plans need to be resubmitted reflecting the actual installation.
|