FIR10-00595
| FIR-Aging Inspection | 3/21/2011 | 3/21/2011 | 3/28/2011 8:50:13 AM | | NR |
|
|
Work is in progress
|
FIR09-00051
| FIR-Aging Inspection | 3/21/2011 | 3/21/2011 | 3/28/2011 8:49:27 AM | | CANC |
|
|
Contractor has been bought by Taylor Brothers. The owner stated that they were taking care of General Fire permits.
|
FIR03-00052
| FIR-Aging Inspection | 3/21/2011 | 3/21/2011 | 3/28/2011 8:47:37 AM | | CANC |
|
|
There was no answer at the contact phone number.
|
BLD11-00005
| FIRE-Final Inspection | 3/21/2011 | 3/21/2011 | 3/21/2011 3:37:39 PM | P | FAIL |
|
|
Repair the two exit signs in the sales area. Repair or provide new exit sign and emergency lighting in the warehouse area. The smoke evac system functioned correctly but when the duct smoke detector was tested it did not shut down the hvac unit and it did not report to the fire alarm panel.
|
FIR11-00077
| INSP-Sprinkler Rough-in/Hydro | 3/21/2011 | 3/21/2011 | 3/21/2011 3:33:56 PM | P | PASS |
|
|
The overhead hydro test passed. The remaining sprinkler piping can be covered.
|
FIR11-00126
| INSP-Final Inspection | 3/21/2011 | 3/21/2011 | 3/21/2011 3:32:08 PM | P | FAIL |
|
|
Permit is not ready to final until the ceiling tile has been installed with the sprinkler canopies. Piping is ok to cover.
|
BLD11-00445
| FIRE-Final Inspection | 3/18/2011 | 3/21/2011 | 3/21/2011 1:05:18 PM | P | PASS |
|
|
life safety passed.
|