Inspections for the day of: Friday, March 21, 2014.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-00679 Electrical Rough-In3/21/20143/21/20143/21/2014 3:49:32 PMPPASS
we cannot start this job till after 1:30pm today. Phone #: ###-#### >> Inspection requested via web by Tim Dunlop UL listing confirmed. rough in ok
ELE14-00672 Conference3/21/20143/21/20143/21/2014 3:01:42 PMPDONE
mike Phone #: ###-#### Discussed areas wired by individual not licenced in Idaho. B&B to trace wiring to ensure free of faults and strapping.
ELE13-03116 Final3/21/20143/21/20143/21/2014 1:59:22 PMPNR
Jake-Please call at lease 30 mins prior to insepction Phone #: ###-#### This permit will remain open do to boxes left open in kitchen for future wiring in bird room and patio. Permit for this work has not been pulled yet.
ELE14-00668 Final3/21/20143/21/20143/21/2014 1:19:32 PMPNR
mike Phone #: ###-#### Service hook up only not interior wiring attached to this permit
ELE14-00668 Permanent Service3/21/20143/21/20143/21/2014 12:48:51 PMPPASS
mike Phone #: ###-#### Permit for large shop service only. No interior wiring attached to permit. p/s o/h n ok
ELE13-03265 Final3/21/20143/21/20143/21/2014 12:23:33 PMPPASS
>> Inspection requested via web by David Baker Final ok
ELE13-03390 Final3/20/20143/21/20143/21/2014 10:19:34 AMAPASS
FINAL I''M DONE WITH IT. FINALLY Phone #: ###-#### >> Inspection requested via web by MARK PINNEY
No card posted. Final ok
ELE14-00675 Temporary Service3/20/20143/21/20143/21/2014 9:48:01 AMAPASS
please don''t hit me first thing Phone #: ###-#### >> Inspection requested via web by Neal Rumsey t/s u/g n ok
ELE14-00665 Temporary Service3/20/20143/21/20143/21/2014 9:15:34 AMAFAIL
final on temp power pole, any questions call ###-#### Phone #: ###-#### >> Inspection requested via web by Andy Rose
110.12(B)- Internal parts of electrical equiptment shall be free of debris.
There shall be no damaged parts do to corrosion. All rusted shall be replaced and debris removed.
ELE14-00671 Permanent Service3/20/20143/21/20143/21/2014 8:50:19 AMAPASS
The meter main is installed on the East side of the building and the new 200 amp panel is installed in the west side of the building on the south wall Phone #: ###-#### >> Inspection requested via web by Spencer McLean p/s u/g n ok
GCE14-00040 GCE-Courtesy3/20/20143/21/20143/20/2014 4:01:03 PMADONE
Doug Phone #: ###-#### Discussed using bottom of I-line type panelboard as raceway to access conduits originally installed in concrete below panelboard. 312.8- States as long as adequate space is available for additional wires it can be used.