Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-00712 Electrical Rough-In3/20/20173/21/20173/21/2017 2:13:26 PMPPASS
Walls Phone #: ###-#### Inspection requested via web by Jim Williams...

wall cover ok new office spaces
ELE17-00278 Final3/21/20173/21/20173/21/2017 12:15:34 PMPPASS
Please call Brad (###-####) 30 minutes ahead for access. Phone #: ###-#### Inspection requested via web by Brad Girard...

ok to final
ELE17-00139 Final3/21/20173/21/20173/21/2017 11:46:13 AMPPASS
Access project from back door Phone #: ###-#### Inspection requested via web by Brad Girard...

ok to final
ELE12-02592 Final3/21/20173/21/20173/21/2017 11:27:27 AMPPASS
ok to final
ELE12-02592 ELE-Aging Inspection3/21/20173/21/20173/21/2017 11:27:11 AM DONE
spoke with contractor...no other work was performed
ELE17-00087 Final3/20/20173/21/20173/21/2017 11:09:39 AMPPASS
Customer name-Al ; Jean Jensen Phone #: ###-#### Inspection requested via web by David Seilheimer...

ok to final
ELE17-00666 Electrical Rough-In3/21/20173/21/20173/21/2017 10:43:56 AMPPASS
Homeowner will be home. If you have any questions call Calvin ###-#### Phone #: ###-#### Inspection requested via web by Clay Morgan...

ok to cover
ELE17-00585 Electrical Rough-In3/20/20173/21/20173/21/2017 10:04:43 AMAPASS
Interior wall inspection on West side of building, 4th floor, for cover.
Contact Scott Boden at ###-####
Thank you. Phone #: ###-#### Inspection requested via web by Cathy Duchek...

interior west walls ok.. two conference rooms and break room
ELE17-00562 Final3/17/20173/21/20173/21/2017 8:59:26 AMAPASS
Retrofit exterior fixtures. Phone #: ###-#### Inspection requested via web by David McClellan..

ok to final
ELE17-00729 Final3/20/20173/21/20173/21/2017 8:29:51 AMAFAIL
Timothy Phone #: ###-####...

service for pump house needs grounding fixed...has been cut...250.66, 250.53

outlet in pump house needs GFI protection and cover plate installed

4 square box needs appropriate cover installed to safe off exposed wiring