Inspections for the day of: Wednesday, March 21, 2018.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-00096 ELE-Aging Inspection3/21/20183/21/20183/23/2018 1:38:14 PM PASS
Final ok
ELE18-01044 Final3/20/20183/21/20183/21/2018 2:28:13 PMPPASS
Tom Young is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce
Final ok
ELE18-01044 Electrical Rough-In3/21/20183/21/20183/21/2018 1:15:04 PMPPASS
Tom Young is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce
New sub panel off I-line for welder located in clean room and receptacles located in IT room all surface conduit and fished in. Rough in ok
ELE18-01046 Rough-In Permanent Service3/20/20183/21/20183/21/2018 1:13:07 PMPPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn
Rough in ok cover p/s u/g n ok
ELE18-00174 Final3/21/20183/21/20183/21/2018 11:43:29 AMAFAIL
Phone #: ###-#### Inspection requested via web by Mark M
406.12(5)- Receptacle outlets located in waiting rooms, business office and corridors shall be tamper resistant type.
ELE18-00233 Final3/20/20183/21/20183/21/2018 10:35:25 AMAFAIL
access code 3535 Phone #: ###-#### Inspection requested via web by Paula Gratiot
110.3- Devices shall be connected as per manufacurers instructions. Reverse polarity right of fireplace and receptacle in down bedroom not hot.
110.22- Breakers and disconnecting means for furnaces shall be identified as per which furnace each controls.
210.8- GFCI devices shall be installed in a readily accessible location. laundry behind washer not readiliy accessible.
210.52- A receptacle outlet shall serve wall space 2' of wider in master bedroom. Floor receptacle OK due to pocket door.
422.30- Microwave shall have a disconnecting means. Unable to locate breaker for microwave.
ELE18-00316 Final3/21/20183/21/20183/21/2018 9:48:50 AMAFAIL
Garage code 1001E Phone #: ###-#### Inspection requested via web by Alan Lusk
352.30- PVC service riser shall be secured with in 3' of meter enclosure.
404.9(A)- All switches shall have covers. Bathrooms
422.30- A disconnecting means shall be provided for all appliances. Oven, lockout acceptable as per 110.25.
Secure intersystem bond
ELE18-00281 Final3/20/20183/21/20183/21/2018 9:14:13 AMAPASS
code 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
ELE17-04357 Final3/20/20183/21/20183/21/2018 9:13:46 AMAPASS
code 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok