Inspections for the day of: Friday, March 22, 2002.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MIS02-00055 FIR-Final3/21/20023/22/20023/22/2002 12:00:00 AMAFAIL
change occupant load sing from 287 to 280, repair existing exit signs, add new exit sign at the north east exit door, repair emergency lights, mount and tag all fire extinguishers, provide duct detectors or verification of less that 2000 cfm, provide approved panic hardware on main exit door. 3/22/2002 1:11:45 PM
BLD01-03233 FIRE-Hydro test above ground3/21/20023/22/20023/22/2002 12:00:00 AMAPASS
Underground flush OK 3/22/2002 2:26:09 PM
BLD01-02165 FIRE-Final Inspection3/21/20023/22/20023/22/2002 12:00:00 AMAFAIL
provide inspection tag for fire extinguishers, repair emergency light in mech. room, remove lock or provide exit hardware for cooler door, provide address on street side of building, duct detector does not shut down hvac unit 3/22/2002 10:33:53 AM
BLD02-00006 FIRE-Final Inspection3/21/20023/22/20023/22/2002 12:00:00 AMPFAIL
all items on the correction notice are taken care of except for the addition of one duct detector. I notified builder that approved fire alarm plans will be required for this addition 3/22/2002 2:59:22 PM
BLD02-00008 FIRE-Final Inspection3/21/20023/22/20023/22/2002 12:00:00 AMPPASS
fire life/safety finaled 3/22/2002 2:55:31 PM
BLD01-01956 FIRE-Final Inspection3/22/20023/22/20023/22/2002 12:00:00 AMPPASS
fire life/safety finaled. fire alarm permit to be voided 3/22/2002 4:04:53 PM
BLD01-03233 FIRE-Sprinkler Rough-in3/22/20023/22/20023/22/2002 12:00:00 AMPFAIL
Added by Inspector: 430 On 3/22/2002 2:20:58 PM tenting is incorrect. Spoke with Joe on areas that needed attention. I went back for a reinspection in the afternoon and not all of the issues were taken care of. The sprinkler pipe in the bonus room now has no insulation and the pipe in the main entrance way is concealed by insulation, it must be exposed
FIR01-00630 INSP-Alarm Testing3/22/20023/22/20023/22/2002 12:00:00 AMPDONE
Added by Inspector: 430 On 3/22/2002 4:02:18 PM per contractor and sam rogers fire alarm permit to be voided