Inspections for the day of: Monday, March 22, 2004.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD03-02929 FIRE-Final Inspection3/18/20043/22/20043/22/2004 12:00:00 AMAFAIL
TOM; Phone #: ###-#### Internet Inspection Request from: Darla Downs need sprinkler plans; need emergency lighting; exit signs don't meet IBC requirements for power requirements; post occupant load signs on balcony 3/22/2004 1:02:51 PM
FIR03-00736 INSP-Final Inspection3/19/20043/22/20043/22/2004 12:00:00 AMAPASS
rand; Phone #: ###-#### Internet Inspection Request from: Barbara Moore completed on 3/19 3/22/2004 11:33:41 AM
FIR03-00761 INSP-Final Inspection3/19/20043/22/20043/22/2004 12:00:00 AMAPASS
rand; Phone #: ###-#### Internet Inspection Request from: Barbara Moore completed 3/19 3/22/2004 11:33:51 AM
FIR04-00110 INSP-Final Inspection3/19/20043/22/20043/22/2004 12:00:00 AMAPART
broadie; Phone #: ###-#### Internet Inspection Request from: Barbara Moore okay to cover; exposed combustibles above ceiling and GC will cover with rock - can verify at final 3/22/2004 8:48:59 AM
BLD04-00137 FIRE-Conference3/22/20043/22/20043/22/2004 12:00:00 AMAPART
Met with GC after sprinkler rough-in; fire alarm panel is in supervisory condition - all sprinkler valves are open - will need the panel clear at final; there are duct detectors installed as part of shell; remove deadbolt from rear exit
FIR03-00793 INSP-Final Inspection3/22/20043/22/20043/22/2004 12:00:00 AMPFAIL
john; Phone #: ###-#### Internet Inspection Request from: Barbara Moore Need 6 QR spare sprinkler in spare head box; all heads on 2nd floor changed to QR per plans 3/22/2004 2:29:25 PM
FIR04-00141 INSP-Sprinkler Rough-in/Hydro3/19/20043/22/20043/22/2004 12:00:00 AMPPART
Contact Mike - would like around 2 pm; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley UG stub-in from property line to just inside wall in basement okay to cover 3/22/2004 3:06:49 PM