BLD03-02929
| FIRE-Final Inspection | 3/18/2004 | 3/22/2004 | 3/22/2004 12:00:00 AM | A | FAIL |
|
|
TOM; Phone #: ###-#### Internet Inspection Request from: Darla Downs need sprinkler plans; need emergency lighting; exit signs don't meet IBC requirements for power requirements; post occupant load signs on balcony 3/22/2004 1:02:51 PM
|
FIR03-00736
| INSP-Final Inspection | 3/19/2004 | 3/22/2004 | 3/22/2004 12:00:00 AM | A | PASS |
|
|
rand; Phone #: ###-#### Internet Inspection Request from: Barbara Moore completed on 3/19 3/22/2004 11:33:41 AM
|
FIR03-00761
| INSP-Final Inspection | 3/19/2004 | 3/22/2004 | 3/22/2004 12:00:00 AM | A | PASS |
|
|
rand; Phone #: ###-#### Internet Inspection Request from: Barbara Moore completed 3/19 3/22/2004 11:33:51 AM
|
FIR04-00110
| INSP-Final Inspection | 3/19/2004 | 3/22/2004 | 3/22/2004 12:00:00 AM | A | PART |
|
|
broadie; Phone #: ###-#### Internet Inspection Request from: Barbara Moore okay to cover; exposed combustibles above ceiling and GC will cover with rock - can verify at final 3/22/2004 8:48:59 AM
|
BLD04-00137
| FIRE-Conference | 3/22/2004 | 3/22/2004 | 3/22/2004 12:00:00 AM | A | PART |
|
|
Met with GC after sprinkler rough-in; fire alarm panel is in supervisory condition - all sprinkler valves are open - will need the panel clear at final; there are duct detectors installed as part of shell; remove deadbolt from rear exit
|
FIR03-00793
| INSP-Final Inspection | 3/22/2004 | 3/22/2004 | 3/22/2004 12:00:00 AM | P | FAIL |
|
|
john; Phone #: ###-#### Internet Inspection Request from: Barbara Moore Need 6 QR spare sprinkler in spare head box; all heads on 2nd floor changed to QR per plans 3/22/2004 2:29:25 PM
|
FIR04-00141
| INSP-Sprinkler Rough-in/Hydro | 3/19/2004 | 3/22/2004 | 3/22/2004 12:00:00 AM | P | PART |
|
|
Contact Mike - would like around 2 pm; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley UG stub-in from property line to just inside wall in basement okay to cover 3/22/2004 3:06:49 PM
|