ELE05-04434
| ELE-Aging Inspection | 3/22/2006 | 3/22/2006 | 3/24/2006 9:05:56 AM | | DONE |
|
|
suc
|
ELE05-04571
| Final | 3/22/2006 | 3/22/2006 | 3/22/2006 4:40:34 PM | P | NR |
|
|
Verna -- prefer as late as possible; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong elect having trouble with some circuits, said to call when ready
|
ELE05-04290
| ELE-Aging Inspection | 3/22/2006 | 3/22/2006 | 3/22/2006 4:13:33 PM | | DONE |
|
|
called contr to set up inspection, left message
|
ELE05-04544
| Final | 3/22/2006 | 3/22/2006 | 3/22/2006 3:22:34 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to final
|
ELE06-00887
| Electrical Rough-In | 3/22/2006 | 3/22/2006 | 3/22/2006 2:14:27 PM | P | PASS |
|
|
Cal -- trench reinspection; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong ok to cover u/g
|
ELE06-00416
| Electrical Rough-In | 3/21/2006 | 3/22/2006 | 3/22/2006 1:33:30 PM | P | PASS |
|
|
Please inspect interior walls and ceilings for cover. Please see Tim on site.; Phone #: ###-#### Internet Inspection Request from: todd hall ric walls and hard lids only ok
|
ELE06-00713
| Rough-In Permanent Service | 3/21/2006 | 3/22/2006 | 3/22/2006 12:47:29 PM | P | PASS |
|
|
Bob I will add the 2 bar boxes in the afternoon. n; Phone #: ###-#### Internet Inspection Request from: Shane Vigil corr made. ric ok, p/s u/g n ok
|
ELE06-00796
| Final | 3/20/2006 | 3/22/2006 | 3/22/2006 11:39:51 AM | A | PASS |
|
|
Greg; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong ok to final
|
ELE05-03277
| ELE-Aging Inspection | 3/22/2006 | 3/22/2006 | 3/22/2006 10:28:46 AM | | NR |
|
|
suc
|
ELE06-00130
| Final | 3/21/2006 | 3/22/2006 | 3/22/2006 10:03:58 AM | A | FAIL |
|
|
allen -call 1st for access; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called contr, left corr notice, 408.4 every circuit shall be legibly identified as to its clear, evident, and specific purpose, 314.23 enclosures in finished surfaces shall be rigidly secured (floor and backsplash in kitchen),314.25 each box shall have a cover (closet), BCC walls shall have 3' access for receptacle testing in garage,and closet shelves shall be installed for final inspection to verify light clearance
|
ELE06-00938
| Electrical Rough-In | 3/21/2006 | 3/22/2006 | 3/22/2006 9:03:56 AM | A | PASS |
|
|
UNDERGROUND INSPECTION PLEASE FOR A SWIMMING POOL........THANKS; Phone #: ###-#### Internet Inspection Request from: Barry Kendall u/g conduit ok to cover
|
ELE06-00957
| Temporary Service | 3/21/2006 | 3/22/2006 | 3/22/2006 8:09:13 AM | A | FAIL |
|
|
gene buffington ###-#### called contr, left message, left corr notice, 312.5 conductors entering enclosures shall be protected from abrasion, 310.7 conductors used for direct burial shall be of a type identified for such use
|