Inspections for the day of: Thursday, March 22, 2007.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-04513 Final3/22/20073/22/20073/22/2007 3:29:36 PMPPART
Work performed by Tony Norton. Phone #: ###-#### met contr, shall provide grounding, left corr notice, BCC 4-05-33(A)(B) equipment shall be listed and labelled by a nationally recognized testing laboratory,NOTE correction shall be made within 2 weeks or further action will be taken such as removal of power
ELE05-04325 Final3/22/20073/22/20073/22/2007 2:42:17 PMPPART
jason ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith 1st floor anop ok to final except pool equip room, left corr notice, nec 110.26(F)(1)(b) there shall be no foreign piping systems over dedicated panel space, NOTE: correction shall be made within 2 weeks or firther action will be taken such as removal of power
ELE06-04710 Final3/22/20073/22/20073/22/2007 1:50:32 PMPPASS
Scheduled by a contractor via Hello! on 3/22/2007 at 6:53:39 AM. Contact: ###-####. ok to final
ELE07-00815 Electrical Rough-In3/22/20073/22/20073/22/2007 1:26:24 PMPNR
jim - pls call 45 prior to inspect; Phone #: ###-#### Internet Inspection Request from: Victoria Beall told needed standoffs for edgewise type const, explained 1 1/4"
ELE07-00573 Electrical Rough-In3/22/20073/22/20073/22/2007 12:47:09 PMPPART
Scheduled by a contractor via Hello! on 3/22/2007 at 6:05:58 AM. Contact: ###-####. ok to pour south 1/3 slab
ELE07-00917 Electrical Rough-In3/22/20073/22/20073/22/2007 10:38:50 AMAPASS
Phone #: ###-#### ric ok
ELE07-00905 Electrical Rough-In3/22/20073/22/20073/22/2007 9:59:58 AMAPASS
Please call if there are any questions or problems. Thank you Kevin Phone #: ###-#### ric ok 2 sides no u/g done yet
ELE07-00905 Rough-In Permanent Service3/21/20073/22/20073/22/2007 9:51:28 AMACANC
Please call if there are any questions or problems. Thank you Kevin Phone #: ###-#### see ri and p/s, called contr about service
ELE07-00905 Permanent Service3/22/20073/22/20073/22/2007 9:50:21 AMAFAIL
Please call if there are any questions or problems. Thank you Kevin Phone #: ###-#### duplex shall have only 1 service, called contr
ELE07-00932 Temporary Service3/22/20073/22/20073/22/2007 9:24:56 AMAPASS
Phone #: ###-#### t/s u/g n ok
ELE07-00931 Temporary Service3/22/20073/22/20073/22/2007 9:11:53 AMAPASS
Phone #: ###-#### t/s u/g n ok
ELE07-00791 Electrical Rough-In3/21/20073/22/20073/22/2007 9:01:10 AMAPASS
Scheduled by a contractor via Hello! on 3/21/2007 at 12:41:31 PM. Contact: ###-####. ric ok lower level
ELE06-02896 Electrical Rough-In3/21/20073/22/20073/22/2007 8:25:35 AMAFAIL
Cover on ceiling Phone #: ###-#### called, left correction notice,nec 330.30(B) mc cable shall be strapped within 12" of box, 358.30(A) emt shall be strapped within 3' of box, 110.12(A) unused openings in boxes shall be closed, 410.14(A) fixtures shall not be cord connected unless permitted by 410.30(B) or(C), 348.30 fmc shall be securely fastened by approved means, BCC no ceiling cover shall be done prior to inspection, no lv cables shall be on grid or raceways