Inspections for the day of: Monday, March 22, 2010.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ESC09-00355 General Inspection3/22/20103/22/20103/22/2010 3:58:19 PMPPASS
looked ok
ESC09-00720 General Inspection3/22/20103/22/20103/22/2010 3:57:27 PMPCANC
looked ok
ELE10-00136 Electrical Rough-In3/22/20103/22/20103/22/2010 3:56:50 PMPPASS
ryker Phone #: ###-#### ok to cover concrete encased raceway near building, north side, ok to cover 2 u/g trenches nw of building
ESC09-00786 General Inspection3/22/20103/22/20103/22/2010 3:40:42 PMPPASS
looked ok
ESC10-00028 General Inspection3/22/20103/22/20103/22/2010 3:25:06 PMPPASS
looked ok
ELE10-00569 Rough-In Permanent Service3/22/20103/22/20103/22/2010 3:01:25 PMPCANC
Inspection requested from web by: Emmet Bushman Phone #: ###-#### see ri and p/s
ELE10-00569 Permanent Service3/22/20103/22/20103/22/2010 3:01:07 PMPPASS
Inspection requested from web by: Emmet Bushman Phone #: ###-#### p/s u/g n ok
ELE10-00569 Electrical Rough-In3/22/20103/22/20103/22/2010 2:22:01 PMPFAIL
Inspection requested from web by: Emmet Bushman Phone #: ###-#### called, left correction notice, NEC 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 334.23 cable in attic shall comply with 320.23, BCC shall provide all boxes and make-up, NOTE: corrections shall be made within 5 working days
ELE09-02386 Final3/21/20103/22/20103/22/2010 1:47:54 PMPFAIL
Need final inspection for residence. General Contractor will be on site, building will be open. Call with any questions.
Thanks Kurt Carlson Inspection requested from web by: Kurt Carlson Phone #: ###-#### called, left correction notice NEC 422.31(B) shall provide breaker lockout for dishwasher, exhaust hood, 410.16(C) shall provide 6" clearance from edge of fixture to edge of shelf in bedroom closet, rest ok, pole light done
ELE10-00567 Temporary Service3/22/20103/22/20103/22/2010 12:46:43 PMPPASS
Corrections have been made. Inspection requested from web by: Rhonda Yoast Phone #: ###-#### corrections made, t/s o/h n ok, no esc this project
ELE10-00393 Permanent Service3/22/20103/22/20103/22/2010 12:03:44 PMPPASS
bill Phone #: ###-#### p/s u/g n ok
ELE07-01945 Final3/18/20103/22/20103/22/2010 10:37:14 AMAPASS
Paul ###-#### ok to final, no esc
ELE10-00187 Final3/19/20103/22/20103/22/2010 9:54:09 AMAPASS
Contractor will provide access in the back door Inspection requested from web by: Lloyd Looney Phone #: ###-#### ok to final, no esc
ELE10-00404 Electrical Rough-In3/19/20103/22/20103/22/2010 9:37:18 AMAPASS
kenny Phone #: ###-#### ric ok, no esc, called, said to add 1 room to permit
ELE10-00567 Temporary Service3/19/20103/22/20103/22/2010 9:01:02 AMAFAIL
Inspection requested from web by: Rhonda Yoast Phone #: ###-#### called, left correction notice, NEC 110.12(B) there shall be no broken parts, 406.8(B) 15 & 20 A receptacles in wet locations shall be listed weather resistant type
ELE10-00521 Electrical Rough-In3/19/20103/22/20103/22/2010 8:27:32 AMAFAIL
ug conduit Inspection requested from web by: Lee VanSchoiack Phone #: ###-#### called, left correction notice, NEC 352.26 there shall not be over 360 degree total bend in pvc, 680.10 minimum burial depth shall be 18" within 5' of pool, NOTE: corrections shall be made within 5 working days or further action will be taken