Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-01503 ELE-Aging Inspection3/22/20163/22/20163/22/2016 2:13:14 PM DONE
Spoke with Maria she will call this in for final
ELE16-00895 Final3/22/20163/22/20163/22/2016 2:06:57 PMPPASS
Rod Phone #: ###-#### final ok
ELE16-00895 Electrical Rough-In3/22/20163/22/20163/22/2016 1:55:27 PMPPASS
Rod Phone #: ###-#### r/i ok ul listed products and ok to remove old Merc. vapor ballasts and install LED lamps
ELE16-00382 Final3/22/20163/22/20163/22/2016 12:52:26 PMPPASS
Inspect bathroom heater Phone #: ###-#### Inspection requested via web by David McClellan final ok 1737 broadway including bathroom
ELE16-00794 Final3/22/20163/22/20163/22/2016 12:51:00 PMPPASS
David Phone #: ###-#### final ok 1747 broadway including bathroom
ELE15-03901 Electrical Rough-In3/19/20163/22/20163/22/2016 11:39:49 AMAPASS
Call Joey for inspection of hard lids on 6th, 7th, and 8th floor, as well as 7th floor west interior/exterior walls. Phone #: ###-#### Inspection requested via web by Rafael Castillo r/i ok hard lids 6th and 7th floors ONLY
ELE16-00222 Conference3/21/20163/22/20163/22/2016 10:39:52 AMADONE
Alan Phone #: ###-#### discuss change out of existing gear and installing new 120/208 volt 1200 amp main disconnect and distribution in basement. Need to get Fire Marshall ok for main disconnect location. Meet NEC 230.70(A)(1) and 230.6(1)or(2). Main disconnect shall be in a readily accessable location
ELE16-00889 Electrical Rough-In3/21/20163/22/20163/22/2016 9:26:11 AMAPASS
Phone #: ###-#### Inspection requested via web by Nick Larson r/i ok new service installed and hooked back up without inspection. Inspected and is ok. Told contractor get p/s inspection next time and let power company hook back up
ELE16-00886 Conference3/21/20163/22/20163/22/2016 9:05:37 AMADONE
Bud Phone #: ###-#### discuss new detached garage with new 200 amp service and 200 amp sub feed to house. Go over trench depth, grounding, separation of grounded conductor at house sub panel and garage wiring and service entrance requirments