FIR15-00822
| INSP-Sprinkler Rough-in/Hydro | 3/21/2016 | 3/22/2016 | 3/22/2016 2:02:26 PM | P | PART |
|
|
Underground hydro test passed. Overhead rough-in failed due to the approved plans not matching the installation such as riser nipples installed where none are shown. Also missing branch line restraints. Plan modifications are required showing all piping changes and the additional fittings in the mains and branchlines.
|
BLD16-00298
| FIRE-Final Inspection | 3/22/2016 | 3/22/2016 | 3/22/2016 1:16:11 PM | P | PASS |
|
|
Life safety passed. I noted single row racks but they did not measure over 8' vertical and the storage was under 12' at the time of inspection.
|
NAF15-00043
| INSP-Sprinkler Rough-in | 3/21/2016 | 3/22/2016 | 3/22/2016 11:39:39 AM | P | FAIL |
|
|
Plan modifications needed due to extensive changes needed such as adding upright sprinkler coverage that is missing is some locations and additional fittings have been added in the mains and riser nipples.
|
BLD16-00477
| FIRE-Final Inspection | 3/21/2016 | 3/22/2016 | 3/22/2016 8:19:24 AM | A | PASS |
|
|
life safety passed
|