ELE08-01084
| ELE-Aging Inspection | 3/22/2017 | 3/22/2017 | 3/22/2017 3:07:33 PM | | PASS |
|
|
Drove by new roof, siding, possible solar on roof, posted notice to please call Daryl DeGrange for update on progress of job.
|
ELE17-00746
| Temporary Service | 3/21/2017 | 3/22/2017 | 3/22/2017 12:57:30 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Emmet Bushman t/s o/h n ok
|
ELE17-00302
| Electrical Rough-In | 3/21/2017 | 3/22/2017 | 3/22/2017 11:20:28 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Tracy Robertson Looked at service, OK, waiting on available fault current. Rough in ok cover
|
ELE17-00751
| Rough-In Permanent Service | 3/22/2017 | 3/22/2017 | 3/22/2017 10:30:20 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov 110.3 440.6- Furnace in garage shall have supply of 20 amp circuit nd 12 ga. wire minimum as per manufacturers instructions. 210.52- Wall space shall have receptacle outlets located so no point measured along floor line is more than 6' from receptacle. Down bed, within 6' of pocket door, Up loft along family room rail. 300.4- MN cable shall not be installed where subject to physical damage. Both fireplace location NM cable near flue. Nail plate ENT above panel. 314.17- Open knock out in bath fan box shall be closed. 314.25- Master shower can secure box cover. 590.6- 50 amp temp receptacle, GFCI not working.
|
ELE17-00741
| Rough-In Permanent Service | 3/21/2017 | 3/22/2017 | 3/22/2017 8:55:35 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk Rough in ok cover p/s u/g n ok
|