Inspections for the day of: Wednesday, March 22, 2017.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-01084 ELE-Aging Inspection3/22/20173/22/20173/22/2017 3:07:33 PM PASS
Drove by new roof, siding, possible solar on roof, posted notice to please call Daryl DeGrange for update on progress of job.
ELE17-00746 Temporary Service3/21/20173/22/20173/22/2017 12:57:30 PMPPASS
Phone #: ###-#### Inspection requested via web by Emmet Bushman
t/s o/h n ok
ELE17-00302 Electrical Rough-In3/21/20173/22/20173/22/2017 11:20:28 AMAPASS
Phone #: ###-#### Inspection requested via web by Tracy Robertson
Looked at service, OK, waiting on available fault current. Rough in ok cover
ELE17-00751 Rough-In Permanent Service3/22/20173/22/20173/22/2017 10:30:20 AMAFAIL
Phone #: ###-#### Inspection requested via web by daniel bibikov
110.3 440.6- Furnace in garage shall have supply of 20 amp circuit nd 12 ga. wire minimum as per manufacturers instructions.
210.52- Wall space shall have receptacle outlets located so no point measured along floor line is more than 6' from receptacle. Down bed, within 6' of pocket door, Up loft along family room rail.
300.4- MN cable shall not be installed where subject to physical damage. Both fireplace location NM cable near flue. Nail plate ENT above panel.
314.17- Open knock out in bath fan box shall be closed.
314.25- Master shower can secure box cover.
590.6- 50 amp temp receptacle, GFCI not working.
ELE17-00741 Rough-In Permanent Service3/21/20173/22/20173/22/2017 8:55:35 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk
Rough in ok cover p/s u/g n ok