Inspections for the day of: Wednesday, March 22, 2017.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR17-00001 INSP-Sprinkler Rough-in/Hydro3/22/20173/22/20173/22/2017 3:46:46 PMPPASS
Underground hydrostatic test complete
FIR16-00760 INSP-Sprinkler Rough-in/Hydro3/22/20173/22/20173/22/2017 3:46:21 PMPPASS
Underground hydrostatic test complete
FIR17-00130 INSP-Sprinkler Rough-in/Hydro3/22/20173/22/20173/22/2017 3:45:58 PMPPASS
Underground hydrostatic test complete
FIR17-00001 INSP-Supply line flush3/21/20173/22/20173/22/2017 2:48:52 PMPCANC
Incorrect inspection request, request is for an underground hydro, this request cancelled and the correct request generated.
FIR16-00760 INSP-Supply line flush3/21/20173/22/20173/22/2017 2:48:31 PMPCANC
Incorrect inspection request, request is for an underground hydro, this request cancelled and the correct request generated.
FIR17-00130 INSP-Supply line flush3/21/20173/22/20173/22/2017 2:48:12 PMPCANC
Incorrect inspection request, request is for an underground hydro, this request cancelled and the correct request generated.
FIR16-00512 INSP-Sprinkler Rough-in/Hydro3/21/20173/22/20173/22/2017 2:45:06 PMPPART
Hydrostatic test for overhead fire sprinkler piping complete for levels 2, 3 and 4, level one did not pass hydrostatic test, visible leak on the overhead fire sprinkler piping as well as pressure loss at gauge. Rough to cover inspection complete for levels 1 and 2, levels 1 and 2 approved for cover. Rough in inspection complete for levels 3 and 4, partial cover allowed on level 3, fire sprinkler piping located in attic space cannot be covered until tenting inspection is complete, overhead fire sprinkler piping in attic space cannot be covered until tenting inspection is complete.
BLD13-03142 BLD-Final3/22/20173/22/20173/22/2017 2:37:58 PMPPASS
As per Building Official, racking system has been approved. Final life fire safety inspection passed/complete.
FIR16-00101 INSP-Sprinkler Rough-in/Hydro3/21/20173/22/20173/22/2017 1:28:54 PMAPASS
Rough to cover inspection for level 1 complete, approved for cover. Hydrostatic test for overhead fire sprinkler piping on level 1 complete.
BLD15-04468 FIRE-Conference3/22/20173/22/20173/22/2017 1:27:57 PMPCANC
Conference rescheduled for 23MAR2017
BLD17-00613 FIRE-Final Inspection3/16/20173/22/20173/22/2017 10:46:40 AMAPASS
No fire sprinklers, no fire alarms, fire extinguisher is in place with a current inspection tag. Noted that front entry has thumbturn deadbolt (Door signage is in place) as well as round type door hardware. Rear exit door has flush mount slide bolt that was removed during inspection, rear exit has round type door hardware as well. Final life fire safety inspection passed/complete.