Inspections for the day of: Tuesday, March 23, 1999.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD97-00441 INSP-Final Inspection3/22/19993/23/19993/23/1999 12:00:00 AMAFAIL
###-#### SAM//FINAL FIRE core not complete; generator test; fan controls;
BLD97-00441 INSP-Alarm Testing3/19/19993/23/19993/23/1999 12:00:00 AMAFAIL
###-#### BOB//FIRE ALARM INSPECT elevators not ready; smoke evac controls not supervised; strobe in lobby not right cd; fire phones have static; labels on panel not correct
BLD97-03173 INSP-Conference3/22/19993/23/19993/23/1999 12:00:00 AMAPART
Jeff Langan at ###-####. discussed final requirements; smoke test; alarms for TI's not okay; lobbys needed
BLD98-03879 INSP-Alarm Testing3/19/19993/23/19993/23/1999 12:00:00 AMAFAIL
###-#### BOB//FIRE ALARM 2ND FLOOR NAC's not supervised
BLD98-03884 INSP-Alarm Testing3/19/19993/23/19993/23/1999 12:00:00 AMAFAIL
###-#### BOB//FIRE ALARM 3RD & 4TH FLOOR NAC's not supervised