BLD03-02405
| FIRE-Final Inspection | 3/22/2004 | 3/23/2004 | 3/23/2004 12:00:00 AM | A | PART |
|
|
Life safety given a temporary occupancy with dave millers permission until the curbing gets painted for fire dept access 3/23/2004 8:08:53 AM
|
BLD04-00099
| FIRE-Final Inspection | 3/22/2004 | 3/23/2004 | 3/23/2004 12:00:00 AM | A | PASS |
|
|
fire life safety finaled 3/23/2004 9:52:16 AM
|
MIS04-00094
| FIR-Final | 3/22/2004 | 3/23/2004 | 3/23/2004 12:00:00 AM | A | PASS |
|
|
fire life safety finaled 3/23/2004 8:35:25 AM
|
FIR04-00158
| INSP-Final Inspection | 3/22/2004 | 3/23/2004 | 3/23/2004 12:00:00 AM | A | PASS |
|
|
fire sprinklers finaled 3/23/2004 9:51:30 AM
|
FIR03-00588
| INSP-Final Inspection | 3/22/2004 | 3/23/2004 | 3/23/2004 12:00:00 AM | A | FAIL |
|
|
Hvac units did not shut down upon activation of the duct smoke detectors. Rewire and retest. Provide knox key box. Mount map. Provide singage on the storage room door showing fire alarm/fire sprinkler riser 3/23/2004 10:22:38 AM
|
BLD03-02407
| FIRE-Final Inspection | 3/22/2004 | 3/23/2004 | 3/23/2004 12:00:00 AM | A | PART |
|
|
Life safety finaled 3/23/2004 8:09:08 AM
|
FIR03-00734
| INSP-Final Inspection | 3/22/2004 | 3/23/2004 | 3/23/2004 12:00:00 AM | P | FAIL |
|
|
I spoke with kevin filer (ansul ###-####) and he stated that the ansul system would not be listed unless it was used throughout the hood. Not just over the appliances. Contractor will need to modify the system per manufactures recommendations. 3/23/2004 3:20:41 PM
|
FIR04-00063
| INSP-Final Inspection | 3/23/2004 | 3/23/2004 | 3/23/2004 12:00:00 AM | P | FAIL |
|
|
General contractor needs to finish installing ceiling tile around the sprinkler pendants 3/23/2004 10:20:17 AM
|
FIR04-00154
| INSP-Sprinkler Rough-in | 3/23/2004 | 3/23/2004 | 3/23/2004 12:00:00 AM | P | CANC |
|
|
rescheduled for tomorrow morning 3/23/2004 3:12:04 PM
|
FIR04-00180
| INSP-Final Inspection | 3/23/2004 | 3/23/2004 | 3/23/2004 12:00:00 AM | P | PASS |
|
|
fire sprinkler finaled 3/23/2004 1:56:03 PM
|
BLD03-01356
| FIRE-Final Inspection | 3/23/2004 | 3/23/2004 | 3/23/2004 12:00:00 AM | P | PASS |
|
|
fire life safety finaled
|
FIR04-00040
| INSP-Final Inspection | 3/23/2004 | 3/23/2004 | 3/23/2004 12:00:00 AM | P | FAIL |
|
|
Door holders did not release. Contractor did not define zones 18, 19 and 20 with the monitoring company. Signals will need to be verified on these zones. Need nfpa 72 forms.
|
FIR02-00294
| INSP-Final Inspection | 3/23/2004 | 3/23/2004 | 3/23/2004 12:00:00 AM | P | PASS |
|
|
|
FIR04-00003
| INSP-Final Inspection | 3/19/2004 | 3/23/2004 | 3/23/2004 12:00:00 AM | P | FAIL |
|
|
Hood suppresion system operated but did not shut off the electrical to the appliances. the gas valve did work. Pull station to be tested on the next inspection 3/23/2004 4:30:40 PM 3/23/2004 4:30:56 PM
|
FIR04-00040
| INSP-Final Inspection | 3/22/2004 | 3/23/2004 | 3/23/2004 12:00:00 AM | P | FAIL |
|
|
Unable to verify signals, missing smoke detector for door release. Verify induct smoke detector work was performed 3/23/2004 1:39:43 PM
|