Inspections for the day of: Tuesday, March 23, 2004.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD03-02405 FIRE-Final Inspection3/22/20043/23/20043/23/2004 12:00:00 AMAPART
Life safety given a temporary occupancy with dave millers permission until the curbing gets painted for fire dept access 3/23/2004 8:08:53 AM
BLD04-00099 FIRE-Final Inspection3/22/20043/23/20043/23/2004 12:00:00 AMAPASS
fire life safety finaled 3/23/2004 9:52:16 AM
MIS04-00094 FIR-Final3/22/20043/23/20043/23/2004 12:00:00 AMAPASS
fire life safety finaled 3/23/2004 8:35:25 AM
FIR04-00158 INSP-Final Inspection3/22/20043/23/20043/23/2004 12:00:00 AMAPASS
fire sprinklers finaled 3/23/2004 9:51:30 AM
FIR03-00588 INSP-Final Inspection3/22/20043/23/20043/23/2004 12:00:00 AMAFAIL
Hvac units did not shut down upon activation of the duct smoke detectors. Rewire and retest. Provide knox key box. Mount map. Provide singage on the storage room door showing fire alarm/fire sprinkler riser 3/23/2004 10:22:38 AM
BLD03-02407 FIRE-Final Inspection3/22/20043/23/20043/23/2004 12:00:00 AMAPART
Life safety finaled 3/23/2004 8:09:08 AM
FIR03-00734 INSP-Final Inspection3/22/20043/23/20043/23/2004 12:00:00 AMPFAIL
I spoke with kevin filer (ansul ###-####) and he stated that the ansul system would not be listed unless it was used throughout the hood. Not just over the appliances. Contractor will need to modify the system per manufactures recommendations. 3/23/2004 3:20:41 PM
FIR04-00063 INSP-Final Inspection3/23/20043/23/20043/23/2004 12:00:00 AMPFAIL
General contractor needs to finish installing ceiling tile around the sprinkler pendants 3/23/2004 10:20:17 AM
FIR04-00154 INSP-Sprinkler Rough-in3/23/20043/23/20043/23/2004 12:00:00 AMPCANC
rescheduled for tomorrow morning 3/23/2004 3:12:04 PM
FIR04-00180 INSP-Final Inspection3/23/20043/23/20043/23/2004 12:00:00 AMPPASS
fire sprinkler finaled 3/23/2004 1:56:03 PM
BLD03-01356 FIRE-Final Inspection3/23/20043/23/20043/23/2004 12:00:00 AMPPASS
fire life safety finaled
FIR04-00040 INSP-Final Inspection3/23/20043/23/20043/23/2004 12:00:00 AMPFAIL
Door holders did not release. Contractor did not define zones 18, 19 and 20 with the monitoring company. Signals will need to be verified on these zones. Need nfpa 72 forms.
FIR02-00294 INSP-Final Inspection3/23/20043/23/20043/23/2004 12:00:00 AMPPASS
FIR04-00003 INSP-Final Inspection3/19/20043/23/20043/23/2004 12:00:00 AMPFAIL
Hood suppresion system operated but did not shut off the electrical to the appliances. the gas valve did work. Pull station to be tested on the next inspection 3/23/2004 4:30:40 PM 3/23/2004 4:30:56 PM
FIR04-00040 INSP-Final Inspection3/22/20043/23/20043/23/2004 12:00:00 AMPFAIL
Unable to verify signals, missing smoke detector for door release. Verify induct smoke detector work was performed 3/23/2004 1:39:43 PM