Inspections for the day of: Wednesday, March 23, 2005.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-00774 Rough-In Permanent Service3/22/20053/23/20053/23/2005 12:00:00 AMAPASS
darrell; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr about gec on same bus as gnded conductor. ric ok, p/s o/h n ok 3/23/2005 8:48:46 AM
ELE04-02595 Electrical Rough-In3/22/20053/23/20053/23/2005 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 3/22/2005 at 3:52:57 PM. Contact: ###-####. clg for lobby,common area ok to cover 3/23/2005 10:11:26 AM
ELE05-00932 Rough-In Permanent Service3/22/20053/23/20053/23/2005 12:00:00 AMAPASS
Internet Inspection Request from: Bob Glenn ric ok, p/s u/g n ok 3/23/2005 7:36:29 AM
ELE05-00933 Rough-In Permanent Service3/22/20053/23/20053/23/2005 12:00:00 AMAPASS
Internet Inspection Request from: Bob Glenn called contr about too many nm thru hole over panel, too many wires under staple, hall recpt, kitchen wire thru floor, and verify recpt by sink, and cautioned about gas pipe over panel as it barely clears. ric ok, p/s u/g n ok 3/23/2005 8:17:08 AM
ELE05-00259 Final3/22/20053/23/20053/23/2005 12:00:00 AMAPASS
Garage code is 8607 or 1234; Phone #: ###-#### Internet Inspection Request from: Joe Thomas called contr to flush up wall plates. ok to final 3/23/2005 9:48:00 AM
ELE05-00331 Final3/22/20053/23/20053/23/2005 12:00:00 AMAPART
gargae code is 8607 or 1234; Phone #: ###-#### Internet Inspection Request from: Joe Thomas called contr about gap at microwave recpt. ok to final 3/23/2005 9:43:21 AM
ELE05-00739 Electrical Rough-In3/23/20053/23/20053/23/2005 12:00:00 AMPPASS
STEVE WALL COVER INSPECTION; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy ok to cover walls only 3/23/2005 4:31:13 PM
ELE05-00966 Rough-In Permanent Service3/23/20053/23/20053/23/2005 12:00:00 AMPPART
brian-- ###-#### called contr, left corr notice, 334.80,adjust ampacity over panel,210.52 (H) entry shall have rcpt, 210.52(A)(2) dining room and loft shall have rcpt for 2' wall space p/s u/g n ok 3/23/2005 3:26:26 PM
ELE05-00903 Electrical Rough-In3/23/20053/23/20053/23/2005 12:00:00 AMPPASS
ok to pour slab only
ELE05-00950 Rough-In Permanent Service3/22/20053/23/20053/23/2005 12:00:00 AMPPASS
gene ###-#### ric ok , p/s u/g n ok 3/23/2005 1:39:08 PM
ELE05-00949 Rough-In Permanent Service3/22/20053/23/20053/23/2005 12:00:00 AMPPASS
gene ###-#### ric ok p/s u/g n ok 3/23/2005 1:39:51 PM
ELE05-00659 Final3/22/20053/23/20053/23/2005 12:00:00 AMPPART
Phone #: ###-#### Internet Inspection Request from: Sean DeLacy all but panels done. will call for am 3/23/2005 12:34:51 PM