Inspections for the day of: Thursday, March 23, 2006.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-04569 ELE-Aging Inspection3/23/20063/23/20063/23/2006 4:41:04 PM DONE
called contr to see if done, but suc
ELE06-00248 Electrical Rough-In3/23/20063/23/20063/23/2006 4:31:40 PMPPASS
POOL LIGHT POTTING COMPOUND; Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack pool light potting ok, need to see rest of u/g before cover
ELE05-04602 ELE-Aging Inspection3/23/20063/23/20063/23/2006 4:05:42 PM DONE
called contr to call for final
ELE06-00966 Temporary Service3/23/20063/23/20063/23/2006 3:24:27 PMAFAIL
Scheduled by a contractor via Hello! on 3/23/2006 at 6:56:48 AM. Contact: ###-####. called contr, left corr notice, 312.5 conductors entering enclosures shall have abrasion protection, 250.53(G) upper end of electrode shall be flush with ground, 250.24(A) grounding electrode conductor shall be connected to grounded conductor terminal, fee due
ELE06-00965 Temporary Service3/23/20063/23/20063/23/2006 3:23:47 PMAFAIL
Scheduled by a contractor via Hello! on 3/23/2006 at 6:56:13 AM. Contact: ###-####. called contr, left corr notice, 312.5 conductors entering enclosures shall have abrasion protection, fee due
ELE06-00964 Temporary Service3/23/20063/23/20063/23/2006 3:22:50 PMAFAIL
Scheduled by a contractor via Hello! on 3/23/2006 at 6:55:39 AM. Contact: ###-####. called contr, left corr notice, 312.5 conductors entering enclosures shall have abrasion protection, 250.53(G) upper end of electrode shall be flush with ground, fee due
ELE06-00963 Temporary Service3/23/20063/23/20063/23/2006 3:21:51 PMAFAIL
Scheduled by a contractor via Hello! on 3/23/2006 at 6:54:52 AM. Contact: ###-####. called contr, left corr notice, 312.5 conductors entering enclosures shall have abrasion protection, fee due
ELE06-00962 Temporary Service3/23/20063/23/20063/23/2006 3:20:37 PMAFAIL
Scheduled by a contractor via Hello! on 3/23/2006 at 6:54:15 AM. Contact: ###-####. called contractor, left corr notice, 312.5 conductors entering enclosures shall have abrasion protection, 250.53(G) upper end of electrode shall be flush with ground, 250.24(A) grounding electrode conductor shall be connected to grounded conductor terminal, fee due
ELE06-00961 Temporary Service3/23/20063/23/20063/23/2006 3:19:41 PMAFAIL
Scheduled by a contractor via Hello! on 3/23/2006 at 6:53:38 AM. Contact: ###-####. called contr, left corr notice, 312.5 conductors entering enclosures shall have abrasion protection,250.8 grounding and bonding jumper shall be connected by pressure connector,fee due
ELE05-04571 Final3/23/20063/23/20063/23/2006 3:15:31 PMPPASS
Scheduled by a contractor via Hello! on 3/23/2006 at 7:40:06 AM. Contact: ###-####. ok to final
ELE06-00957 Temporary Service3/23/20063/23/20063/23/2006 2:26:44 PMPPASS
Gene; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong t/s u/g n ok
ELE06-00671 Electrical Rough-In3/23/20063/23/20063/23/2006 1:46:44 PMPPART
Tye; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong ne wall ok to pour
ELE06-00592 Final3/22/20063/23/20063/23/2006 12:29:44 PMPPASS
Chris; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong /// Reschedule for 3-23-06 PM per Chris (Superior Electric) 3-22-06 eus ok to final, signed occ card
ELE05-04514 Final3/22/20063/23/20063/23/2006 9:42:14 AMAFAIL
Jari; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong called contr, left corr notice, 110.3(B) disposal shall be installed in accordance with instructions, sensor shall operate lights
ELE06-00301 Final3/22/20063/23/20063/23/2006 9:34:48 AMAFAIL
Jari; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong called contr, left message, 110.3(B) disposal shall be installed in accordance with instructions
ELE06-00113 Electrical Rough-In3/21/20063/23/20063/23/2006 8:40:35 AMAPART
7TH FLOOR ROUGH-IN CONTACT GREG PACK; Phone #: ###-#### Internet Inspection Request from: Shelli Daylong 7th floor walls anop ok to cover
ELE06-00960 Permanent Service3/21/20063/23/20063/22/2006 12:00:00 AMPCANC
as early pm as possible please//scott davis ###-####\\Will call and reschedule.