Inspections for the day of: Friday, March 23, 2007.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-00447 Electrical Rough-In3/23/20073/23/20073/23/2007 3:06:18 PMPPART
glenn - women''''s restroom ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith walls and ceiling ok
ELE07-00970 Conference3/23/20073/23/20073/23/2007 2:38:25 PMPDONE
###-#### wylie cell ok
ELE07-00056 Final3/23/20073/23/20073/23/2007 1:47:25 PMPCANC
Jay ###-#### talked with contractor not ready he needs to get p/s called in for Idpo, on other permit before final can be done
ELE07-00964 Temporary Service3/23/20073/23/20073/23/2007 1:20:31 PMPFAIL
Phone #: ###-#### corr called loose acorn fitting, use conn for GEC, 250.24 terminate GEC to neutral bus not equip grd bus
ELE06-04227 Final3/23/20073/23/20073/23/2007 12:45:20 PMPNR
Lars; Phone #: ###-#### Internet Inspection Request from: Stacie Backus needs under counter lights installed kit. called
ELE06-04690 Final3/23/20073/23/20073/23/2007 12:21:54 PMPFAIL
Robert; Phone #: ###-#### Internet Inspection Request from: Stacie Backus
corr. fee due 300.10&12 maintain elect,& mech continuity for mc at high bay fixtures, ID white wire mc in subpanel 20 amp 2pole breaker
ELE07-00910 Rough-In Permanent Service3/23/20073/23/20073/23/2007 11:41:37 AMAPASS
Scheduled by a contractor via Hello! on 3/23/2007 at 5:15:48 AM. Contact: ###-####. r/i p/s u/g new ok
ELE07-00927 Rough-In Permanent Service3/23/20073/23/20073/23/2007 10:58:20 AMAPASS
Scheduled by a contractor via Hello! on 3/23/2007 at 5:14:29 AM. Contact: ###-####. r/i p/s u/g new ok
ELE06-03179 Final3/22/20073/23/20073/23/2007 10:17:54 AMAFAIL
jeremy Note: please call 1st for access; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr. called fee due 400.8(2&5) cord shall not pass through ceiling, support all cables in area where work was done above grid ceiling
ELE07-00960 Electrical Rough-In3/22/20073/23/20073/23/2007 9:35:40 AMAFAIL
Phone #: ###-#### corr. do not cover called 300.4(A)(1) nail plate for all areas, 210.52(B) shall not use small appliance circuit to feed new office addition
ELE07-00951 Conference3/22/20073/23/20073/23/2007 8:43:46 AMADONE
Brandon pls call 30 min prior; Phone #: ###-#### Internet Inspection Request from: Stacie Backus ok
ELE07-00486 Final3/23/20073/23/20073/23/2007 8:31:22 AMAPASS
ok no card
ELE07-00624 Final3/22/20073/23/20073/23/2007 8:11:54 AMAPART
Raelene; Phone #: ###-#### Internet Inspection Request from: Stacie Backus
t/o for phase 1 ok only no card