ELE07-00447
| Electrical Rough-In | 3/23/2007 | 3/23/2007 | 3/23/2007 3:06:18 PM | P | PART |
|
|
glenn - women''''s restroom ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith walls and ceiling ok
|
ELE07-00970
| Conference | 3/23/2007 | 3/23/2007 | 3/23/2007 2:38:25 PM | P | DONE |
|
|
###-#### wylie cell ok
|
ELE07-00056
| Final | 3/23/2007 | 3/23/2007 | 3/23/2007 1:47:25 PM | P | CANC |
|
|
Jay ###-#### talked with contractor not ready he needs to get p/s called in for Idpo, on other permit before final can be done
|
ELE07-00964
| Temporary Service | 3/23/2007 | 3/23/2007 | 3/23/2007 1:20:31 PM | P | FAIL |
|
|
Phone #: ###-#### corr called loose acorn fitting, use conn for GEC, 250.24 terminate GEC to neutral bus not equip grd bus
|
ELE06-04227
| Final | 3/23/2007 | 3/23/2007 | 3/23/2007 12:45:20 PM | P | NR |
|
|
Lars; Phone #: ###-#### Internet Inspection Request from: Stacie Backus needs under counter lights installed kit. called
|
ELE06-04690
| Final | 3/23/2007 | 3/23/2007 | 3/23/2007 12:21:54 PM | P | FAIL |
|
|
Robert; Phone #: ###-#### Internet Inspection Request from: Stacie Backus corr. fee due 300.10&12 maintain elect,& mech continuity for mc at high bay fixtures, ID white wire mc in subpanel 20 amp 2pole breaker
|
ELE07-00910
| Rough-In Permanent Service | 3/23/2007 | 3/23/2007 | 3/23/2007 11:41:37 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 3/23/2007 at 5:15:48 AM. Contact: ###-####. r/i p/s u/g new ok
|
ELE07-00927
| Rough-In Permanent Service | 3/23/2007 | 3/23/2007 | 3/23/2007 10:58:20 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 3/23/2007 at 5:14:29 AM. Contact: ###-####. r/i p/s u/g new ok
|
ELE06-03179
| Final | 3/22/2007 | 3/23/2007 | 3/23/2007 10:17:54 AM | A | FAIL |
|
|
jeremy Note: please call 1st for access; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr. called fee due 400.8(2&5) cord shall not pass through ceiling, support all cables in area where work was done above grid ceiling
|
ELE07-00960
| Electrical Rough-In | 3/22/2007 | 3/23/2007 | 3/23/2007 9:35:40 AM | A | FAIL |
|
|
Phone #: ###-#### corr. do not cover called 300.4(A)(1) nail plate for all areas, 210.52(B) shall not use small appliance circuit to feed new office addition
|
ELE07-00951
| Conference | 3/22/2007 | 3/23/2007 | 3/23/2007 8:43:46 AM | A | DONE |
|
|
Brandon pls call 30 min prior; Phone #: ###-#### Internet Inspection Request from: Stacie Backus ok
|
ELE07-00486
| Final | 3/23/2007 | 3/23/2007 | 3/23/2007 8:31:22 AM | A | PASS |
|
|
ok no card
|
ELE07-00624
| Final | 3/22/2007 | 3/23/2007 | 3/23/2007 8:11:54 AM | A | PART |
|
|
Raelene; Phone #: ###-#### Internet Inspection Request from: Stacie Backus t/o for phase 1 ok only no card
|