ELE07-00967
| Electrical Rough-In | 3/23/2007 | 3/23/2007 | 3/23/2007 3:44:21 PM | P | PASS |
|
|
John; Phone #: ###-#### Internet Inspection Request from: Stacie Backus ric ok
|
ELE07-00969
| Temporary Service | 3/23/2007 | 3/23/2007 | 3/23/2007 3:13:40 PM | P | PASS |
|
|
t/s u/g n ok
|
ELE07-00969
| Temporary Service | 3/23/2007 | 3/23/2007 | 3/23/2007 3:11:58 PM | P | CANC |
|
|
dan ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
|
ELE07-00663
| Final | 3/23/2007 | 3/23/2007 | 3/23/2007 2:29:38 PM | P | CANC |
|
|
jim; Phone #: ###-####7 Internet Inspection Request from: Cathy Chiles
|
ELE07-00895
| Rough-In Permanent Service | 3/23/2007 | 3/23/2007 | 3/23/2007 1:43:12 PM | P | PASS |
|
|
rough electrical and permanent service inspection ric ok, p/s u/g n ok
|
ELE07-00896
| Rough-In Permanent Service | 3/23/2007 | 3/23/2007 | 3/23/2007 12:59:56 PM | P | PASS |
|
|
rough in inspection and permanent service ric ok, p/s u/g n ok
|
ELE06-03466
| Final | 3/22/2007 | 3/23/2007 | 3/23/2007 11:08:06 AM | A | PASS |
|
|
Four Day Funiture sign over storefront Phone #: ###-#### ok to final
|
ELE05-04325
| Final | 3/22/2007 | 3/23/2007 | 3/23/2007 10:56:47 AM | A | PART |
|
|
jason; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok to final anop, signed t/o card, need to finish roof, fix corr notice, verify panel schedules
|
ELE06-04201
| Permanent Service | 3/22/2007 | 3/23/2007 | 3/23/2007 9:53:12 AM | A | CANC |
|
|
Insp for temp occupancy. Phone #: ###-#### wrong type, see final
|
ELE06-04201
| Final | 3/23/2007 | 3/23/2007 | 3/23/2007 9:52:41 AM | A | PART |
|
|
Insp for temp occupancy. Phone #: ###-#### signed t/o card, left corr notice, nec 408.4 shall complete circuit schedules, 605.7 shall use multi-pole breakers with common trip for furniture, 422.31 shall provide dishwasher disconnect, BCC shall finish panel covers, all equipment shall be listed by a nationally recognized testing laboratory (48v dc)
|
ELE07-00754
| Rough-In Permanent Service | 3/22/2007 | 3/23/2007 | 3/23/2007 8:55:50 AM | A | PASS |
|
|
On-Site contact - Gene ###-#### Phone #: ###-#### ric ok p/s u/g n ok
|
ELE06-02896
| Electrical Rough-In | 3/22/2007 | 3/23/2007 | 3/23/2007 8:05:40 AM | A | PASS |
|
|
reinspection ceiling Phone #: ###-#### corrections made, ok to cover grid ceilings
|