Inspections for the day of: Monday, March 23, 2009.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-01051 INSP-Sprinkler Rough-in3/23/20093/23/20093/25/2009 6:40:48 AMPPART
See plan annotations for areas inspected to date.
BLD07-02112 BLD-Aging Inspection3/23/20093/23/20093/24/2009 12:42:15 PMPPART
Project related fire alarm permit has been finaled, need fire life safety inspection prior to building final.
FIR08-00631 INSP-Sprinkler Rough-in/Hydro3/23/20093/23/20093/23/2009 3:16:07 PMPPART
UG fire supply line hydrostatic testing completed satisfactory. Supply line flush also completed okay post hydro test.
FIR08-00018 INSP-Sprinkler Rough-in/Hydro3/23/20093/23/20093/23/2009 3:11:50 PMPPART
Hydrostatic testing for the 15th, 10th, 2nd floors passed 3/20, hydrostatic retest of the 1st and 8th floor also passed.
FIR08-00821 FIR-Aging Inspection3/23/20093/23/20093/23/2009 2:28:25 PM NR
Pending site inspection request for permit final of work completed.
BLD06-01451 FIRE-Conference3/20/20093/23/20093/23/2009 2:27:34 PMADONE
On site conference regarding correction notice issued 1/30/09 and FIR permit activity note 1/22/09 addressing obstructions to sprinkler discharge such as surface mounted light fixtures. Discussed NFPA 13D 8.2.5 criteria.
BLD06-01451 FIRE-Conference3/20/20093/23/20093/23/2009 2:26:16 PMADONE
On site conference regarding correction notice issued 1/30/09 and FIR permit activity note 1/22/09 addressing obstructions to sprinkler discharge such as surface mounted light fixtures. Discussed NFPA 13D 8.2.5 criteria.
FIR09-00002 INSP-Final Inspection3/20/20093/23/20093/23/2009 2:16:37 PMAFAIL
Functional alarm testing not completed due to incorrect cd settings at two devices and one overspaced notification appliance at the open office area NW corner- locations marked on plans.
FIR08-00104 INSP-Final Inspection3/20/20093/23/20093/23/2009 2:12:05 PMAPASS
Recieved NFPA 72 documents per request, resubmittals verified, fire alarm permit finaled.