FIR07-01051
| INSP-Sprinkler Rough-in | 3/23/2009 | 3/23/2009 | 3/25/2009 6:40:48 AM | P | PART |
|
|
See plan annotations for areas inspected to date.
|
BLD07-02112
| BLD-Aging Inspection | 3/23/2009 | 3/23/2009 | 3/24/2009 12:42:15 PM | P | PART |
|
|
Project related fire alarm permit has been finaled, need fire life safety inspection prior to building final.
|
FIR08-00631
| INSP-Sprinkler Rough-in/Hydro | 3/23/2009 | 3/23/2009 | 3/23/2009 3:16:07 PM | P | PART |
|
|
UG fire supply line hydrostatic testing completed satisfactory. Supply line flush also completed okay post hydro test.
|
FIR08-00018
| INSP-Sprinkler Rough-in/Hydro | 3/23/2009 | 3/23/2009 | 3/23/2009 3:11:50 PM | P | PART |
|
|
Hydrostatic testing for the 15th, 10th, 2nd floors passed 3/20, hydrostatic retest of the 1st and 8th floor also passed.
|
FIR08-00821
| FIR-Aging Inspection | 3/23/2009 | 3/23/2009 | 3/23/2009 2:28:25 PM | | NR |
|
|
Pending site inspection request for permit final of work completed.
|
BLD06-01451
| FIRE-Conference | 3/20/2009 | 3/23/2009 | 3/23/2009 2:27:34 PM | A | DONE |
|
|
On site conference regarding correction notice issued 1/30/09 and FIR permit activity note 1/22/09 addressing obstructions to sprinkler discharge such as surface mounted light fixtures. Discussed NFPA 13D 8.2.5 criteria.
|
BLD06-01451
| FIRE-Conference | 3/20/2009 | 3/23/2009 | 3/23/2009 2:26:16 PM | A | DONE |
|
|
On site conference regarding correction notice issued 1/30/09 and FIR permit activity note 1/22/09 addressing obstructions to sprinkler discharge such as surface mounted light fixtures. Discussed NFPA 13D 8.2.5 criteria.
|
FIR09-00002
| INSP-Final Inspection | 3/20/2009 | 3/23/2009 | 3/23/2009 2:16:37 PM | A | FAIL |
|
|
Functional alarm testing not completed due to incorrect cd settings at two devices and one overspaced notification appliance at the open office area NW corner- locations marked on plans.
|
FIR08-00104
| INSP-Final Inspection | 3/20/2009 | 3/23/2009 | 3/23/2009 2:12:05 PM | A | PASS |
|
|
Recieved NFPA 72 documents per request, resubmittals verified, fire alarm permit finaled.
|