FIR09-00730
| FIR-Aging Inspection | 3/23/2010 | 3/23/2010 | 3/25/2010 8:43:05 AM | | NR |
|
|
Per Charlie with Simplex he was told that this project was canceled. He stated he will follow up and contact stephanie to have the permit voided.
|
FIR09-00708
| INSP-Sprinkler Rough-in | 3/22/2010 | 3/23/2010 | 3/24/2010 2:17:16 PM | P | PART |
|
|
The insulation blocking sprinkler coverage in the soffits has been addressed. All other areas in the lounge/hall areas, as discussed, can be covered. Three small rooms in the nurses station area can not be covered due to sprinkler pipe tenting issues.
|
FIR10-00015
| INSP-Sprinkler Rough-in | 3/23/2010 | 3/23/2010 | 3/24/2010 9:02:16 AM | P | PASS |
|
|
Sprinkler piping is ok to cover.
|
BLD10-00513
| FIRE-Final Inspection | 3/22/2010 | 3/23/2010 | 3/23/2010 2:34:24 PM | P | FAIL |
|
|
See the city approved plans for the locations of deficiencies which include repairing the exit signs over the front doors and providing emergency lighting, providing an ABC and K class fire extinguishers, providing certification for the portable fryer, covering exposed electrical outlets, removing the deadbolt on the rear exit door and providing lever hardware on the same door.
|
FIR10-00088
| INSP-Final Inspection | 3/22/2010 | 3/23/2010 | 3/23/2010 2:32:17 PM | A | PASS |
|
|
Permit finaled. The lights have been removed from under the hood and the manual pull station functioned correctly.
|
FIR09-00635
| INSP-Alarm Testing | 3/22/2010 | 3/23/2010 | 3/23/2010 10:16:15 AM | A | PASS |
|
|
The phase 8 existing fire alarm horns operated. We found that the new a/v's in the main lobby had not been inspected or connected to the NAC panel.
|
FIR10-00106
| INSP-Final Inspection | 3/22/2010 | 3/23/2010 | 3/23/2010 10:14:45 AM | A | PASS |
|
|
Permit finaled.
|
FIR10-00108
| INSP-Final Inspection | 3/23/2010 | 3/23/2010 | 3/23/2010 9:59:00 AM | P | CANC |
|
|
Tim Christopherson Inspection requested from web by: Diane Turner Phone #: ###-#### Inspection cancelled from web by: Diane Turner
|
FIR10-00107
| INSP-Final Inspection | 3/23/2010 | 3/23/2010 | 3/23/2010 9:58:42 AM | P | CANC |
|
|
Tim Christopherson Inspection requested from web by: Diane Turner Phone #: ###-#### Inspection cancelled from web by: Diane Turner
|
BLD09-01423
| FIRE-Final Inspection | 3/22/2010 | 3/23/2010 | 3/23/2010 8:50:22 AM | A | PASS |
|
|
Life safety passed
|