Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00730 FIR-Aging Inspection3/23/20103/23/20103/25/2010 8:43:05 AM NR
Per Charlie with Simplex he was told that this project was canceled. He stated he will follow up and contact stephanie to have the permit voided.
FIR09-00708 INSP-Sprinkler Rough-in3/22/20103/23/20103/24/2010 2:17:16 PMPPART
The insulation blocking sprinkler coverage in the soffits has been addressed. All other areas in the lounge/hall areas, as discussed, can be covered. Three small rooms in the nurses station area can not be covered due to sprinkler pipe tenting issues.
FIR10-00015 INSP-Sprinkler Rough-in3/23/20103/23/20103/24/2010 9:02:16 AMPPASS
Sprinkler piping is ok to cover.
BLD10-00513 FIRE-Final Inspection3/22/20103/23/20103/23/2010 2:34:24 PMPFAIL
See the city approved plans for the locations of deficiencies which include repairing the exit signs over the front doors and providing emergency lighting, providing an ABC and K class fire extinguishers, providing certification for the portable fryer, covering exposed electrical outlets, removing the deadbolt on the rear exit door and providing lever hardware on the same door.
FIR10-00088 INSP-Final Inspection3/22/20103/23/20103/23/2010 2:32:17 PMAPASS
Permit finaled. The lights have been removed from under the hood and the manual pull station functioned correctly.
FIR09-00635 INSP-Alarm Testing3/22/20103/23/20103/23/2010 10:16:15 AMAPASS
The phase 8 existing fire alarm horns operated. We found that the new a/v's in the main lobby had not been inspected or connected to the NAC panel.
FIR10-00106 INSP-Final Inspection3/22/20103/23/20103/23/2010 10:14:45 AMAPASS
Permit finaled.
FIR10-00108 INSP-Final Inspection3/23/20103/23/20103/23/2010 9:59:00 AMPCANC
Tim Christopherson Inspection requested from web by: Diane Turner Phone #: ###-#### Inspection cancelled from web by: Diane Turner
FIR10-00107 INSP-Final Inspection3/23/20103/23/20103/23/2010 9:58:42 AMPCANC
Tim Christopherson Inspection requested from web by: Diane Turner Phone #: ###-#### Inspection cancelled from web by: Diane Turner
BLD09-01423 FIRE-Final Inspection3/22/20103/23/20103/23/2010 8:50:22 AMAPASS
Life safety passed