FIR10-00470
| INSP-Sprinkler Rough-in | 3/23/2011 | 3/23/2011 | 3/23/2011 3:02:04 PM | P | PASS |
|
|
The under mezzanine sprinkler piping, showroom side of wall, is ok to cover.
|
FIR10-00579
| FIR-Aging Inspection | 3/23/2011 | 3/23/2011 | 3/23/2011 2:40:20 PM | P | CANC |
|
|
wrong inspection type set up.
|
FIR10-00579
| INSP-Sprinkler Rough-in | 3/23/2011 | 3/23/2011 | 3/23/2011 2:37:19 PM | P | PASS |
|
|
The lighting obstructions have been addressed and the extended coverage head is ok. Items needing addressed are the typical final inspection items such as tagging, signage, backflow certification and forward flow test.....ect
|
FIR10-00443
| INSP-Final Inspection | 3/22/2011 | 3/23/2011 | 3/23/2011 2:23:41 PM | P | FAIL |
|
|
Provide the missing earthquake bracing at the east end of the system and change the lateral bracing to a longitudinal brace at the 2 1/2" connection point per the plans. Also many of the new sidewall heads exceed 6" down from the deck. Per the detail on the plans the heads are to be installed at 6". There was no data sheet provided to verify if the heads could be up to 10" below the deck as some are installed now.
|
FIR11-00118
| INSP-Final Inspection | 3/23/2011 | 3/23/2011 | 3/23/2011 1:48:57 PM | P | PASS |
|
|
Permit finaled
|
BLD11-00435
| FIRE-Final Inspection | 3/22/2011 | 3/23/2011 | 3/23/2011 10:23:53 AM | A | PASS |
|
|
life safety passed
|