Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00668 INSP-Final Inspection3/20/20123/23/20123/23/2012 3:13:44 PMAFAIL
The zones being reported to the fire alarm panel annunciator do not match those listed on the approved plans. As-built plans are required that match. The zone for the wet system water flow switch reported incorrectly as a smoke detector. This also will need to be changed. The four new duct smoke detectors, as shown on the approved plans, do not shut down the hvac units as required. They will need to be corrected and re-tested.
BLD12-00036 FIRE-Final Inspection3/23/20123/23/20123/23/2012 2:33:19 PMPPASS
life safety passed
FIR12-00111 INSP-Final Inspection3/23/20123/23/20123/23/2012 2:33:02 PMPPASS
Permit finaled
BLD12-00539 FIRE-Final Inspection3/22/20123/23/20123/23/2012 10:52:44 AMAPASS
life safety passed