ELE15-00753
| Final | 3/23/2015 | 3/23/2015 | 3/23/2015 3:52:53 PM | P | PASS |
|
|
Need final inspection for replacing 400 watt lamps w/LED on outside wall packs. Phone #: ###-#### Inspection requested via web by Alan Lusk ok final
|
ELE15-00755
| Final | 3/23/2015 | 3/23/2015 | 3/23/2015 3:10:43 PM | P | PASS |
|
|
Need final inspection for replacing all 400 watt outside lights w/LED lamps. Phone #: ###-#### Inspection requested via web by Alan Lusk ok final
|
ELE15-00730
| Temporary Service | 3/23/2015 | 3/23/2015 | 3/23/2015 2:41:06 PM | P | PASS |
|
|
Darren Phone #: ###-#### t/s u/g n ok
|
ELE15-00729
| Temporary Service | 3/23/2015 | 3/23/2015 | 3/23/2015 2:21:50 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
|
ELE15-00440
| Permanent Service | 3/23/2015 | 3/23/2015 | 3/23/2015 1:44:13 PM | P | FAIL |
|
|
Toby is the contact. Permanent service for Fire Pump. Phone #: ###-#### Inspection requested via web by Buster Bowen called, left message, left correction notice, NEC 358.24 there shall not be more than 360 degree total bend in raceway, 110.3(B) shall install liquid tite per instructions
|
ELE15-00728
| Temporary Service | 3/23/2015 | 3/23/2015 | 3/23/2015 12:57:02 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
|
ELE14-02715
| Final | 3/20/2015 | 3/23/2015 | 3/23/2015 12:29:29 PM | A | PASS |
|
|
Kevin Phone #: ###-#### ok final
|
ELE15-00703
| Electrical Rough-In | 3/22/2015 | 3/23/2015 | 3/23/2015 10:36:59 AM | A | PASS |
|
|
Would like an ok to cover walls. Ceiling light placement not finalized yet. Ceiling is already finished and I will just be putting in can lights w/ shower trim. I have just run to the first light. Thanks Todd Owyhee Electric. After 9:00 A.M. if possible Please Phone #: ###-#### Inspection requested via web by todd cline ri ok
|
ELE15-00553
| Rough-In Permanent Service | 3/23/2015 | 3/23/2015 | 3/23/2015 10:12:18 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn ri ok, p/s u/g n ok
|
ELE15-00747
| Rough-In Permanent Service | 3/20/2015 | 3/23/2015 | 3/23/2015 9:43:19 AM | A | PASS |
|
|
please contact ben if any questions Phone #: ###-#### Inspection requested via web by Ben Archibald ri ok, p/s u/g n ok
|
ELE15-00751
| Rough-In Permanent Service | 3/22/2015 | 3/23/2015 | 3/23/2015 9:01:58 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI called, left correction notice, BCC shall post ESC card, shall post address, shall not cover wiring prior to inspection, 250.24 and 250.64(C) grounding electrode shall be continuous, 334.23 shall protect nm cable within 6' of attic access, 210.70 shall provide light and switch under stairs5tf
|
ELE15-00750
| Electrical Rough-In | 3/22/2015 | 3/23/2015 | 3/23/2015 8:44:17 AM | A | PASS |
|
|
Inspect under ground conduit for cover Phone #: ###-#### Inspection requested via web by Robert Schroder ok cover u/g house to garage only
|
ELE15-00749
| Electrical Rough-In | 3/22/2015 | 3/23/2015 | 3/23/2015 8:02:44 AM | A | PASS |
|
|
Inspect underground conduit for cover Phone #: ###-#### Inspection requested via web by Robert Schroder ok cover u/g house to garage only
|