Inspections for the day of: Monday, March 23, 2015.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00750 INSP-Sprinkler Rough-in3/23/20153/23/20153/31/2015 11:49:49 AMPPART
Overhead inspection completed for the dry system and single line feeds to individual sprinklers at some perimeter rooms fed from the wet system. Refer to approved plans for locations in need of revison including spacing, obstructions, and seismic bracing.
FIR14-00867 INSP-Sprinkler Rough-in3/23/20153/23/20153/23/2015 5:49:40 PMPDEFR
FIR14-00437 INSP-Final Inspection3/23/20153/23/20153/23/2015 5:47:45 PMPPART
Final Inspection above ground
please call Leroy 30 min prior ###-#### Phone #: ###-#### Inspection requested via web by Jacci Hunt
FIR15-00009 INSP-Final Inspection3/20/20153/23/20153/23/2015 5:47:01 PMPFAIL
HVAC units did not shut down upon activation of duct smoke detectors, need to verify necton rating on site per review note comments, noted duct SD are programed as an alarm signal.
BLD14-03482 FIRE-Final Inspection3/19/20153/23/20153/23/2015 5:38:33 PMPPASS
Fire life safety inspection completed acceptable.
FIR15-00065 INSP-Final Inspection3/23/20153/23/20153/23/2015 5:37:03 PMPPASS
Verified added coverage at the14th and 15th floor common area closets. Fire sprinkler permit finaled.
FIR15-00172 INSP-Sprinkler Rough-in/Hydro3/22/20153/23/20153/23/2015 12:41:32 PMANR
Project is not in condition for hood suppression system inspection at this time- construction underway.
FIR14-00483 INSP-Final Inspection3/20/20153/23/20153/23/2015 12:40:04 PMAPASS
Fire sprinkler permit finaled.
BLD14-03402 FIRE-Final Inspection3/20/20153/23/20153/23/2015 12:38:34 PMAFAIL
Items noted include door hardware revisions at the new office and conference room, post fire extinguishers per plan.
FIR14-00886 INSP-Final Inspection3/20/20153/23/20153/23/2015 12:36:21 PMAPASS
Fire sprinkler permit final approved.
FIR15-00172 INSP-Sprinkler Rough-in/Hydro3/22/20153/23/20153/22/2015 10:14:14 AMPCANC
Call Bud Phone #: ###-#### >> Inspection requested via web by Don Kartchner Inspection cancelled from web by: Don Kartchner