ELE13-01035
| ELE-Aging Inspection | 3/23/2016 | 3/23/2016 | 3/24/2016 1:42:23 PM | | DONE |
|
|
too busy
|
ELE16-00838
| Final | 3/18/2016 | 3/23/2016 | 3/23/2016 1:51:33 PM | P | NR |
|
|
Later the better, please call ahead - Hot tub final - Jacob Phone #: ###-#### not ready
|
ELE16-00867
| Conference | 3/22/2016 | 3/23/2016 | 3/23/2016 1:23:06 PM | P | DONE |
|
|
Dan Phone #: ###-#### discuss 240.24 height requirements for Main disconnect . 240.24(A)-calls for 6' 7" maximum. Panelboard rough in can is as low as can be with 4" lip for wash down health dept. requirement. Can't meet code requirement. Told Ben we willlook into this more.
|
ELE15-04007
| Final | 3/22/2016 | 3/23/2016 | 3/23/2016 9:51:20 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI final ok
|
ELE15-03698
| Final | 3/22/2016 | 3/23/2016 | 3/23/2016 8:35:23 AM | A | FAIL |
|
|
Curt Phone #: ###-#### 210.8(B)(5)- 120 volt receptacles within 6 foot of sinks shall have GFCI protection (kitchen). 210.12(A)-all 120 volt outlets (lights, sm.detectors and receptacles) in bdrms. shall have AFCI protection.
|