Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-01035 ELE-Aging Inspection3/23/20163/23/20163/24/2016 1:42:23 PM DONE
too busy
ELE16-00838 Final3/18/20163/23/20163/23/2016 1:51:33 PMPNR
Later the better, please call ahead - Hot tub final - Jacob Phone #: ###-#### not ready
ELE16-00867 Conference3/22/20163/23/20163/23/2016 1:23:06 PMPDONE
Dan Phone #: ###-#### discuss 240.24 height requirements for Main disconnect . 240.24(A)-calls for 6' 7" maximum. Panelboard rough in can is as low as can be with 4" lip for wash down health dept. requirement. Can't meet code requirement. Told Ben we willlook into this more.
ELE15-04007 Final3/22/20163/23/20163/23/2016 9:51:20 AMAPASS
Phone #: ###-#### Inspection requested via web by TOM BICANDI final ok
ELE15-03698 Final3/22/20163/23/20163/23/2016 8:35:23 AMAFAIL
Curt Phone #: ###-#### 210.8(B)(5)- 120 volt receptacles within 6 foot of sinks shall have GFCI protection (kitchen). 210.12(A)-all 120 volt outlets (lights, sm.detectors and receptacles) in bdrms. shall have AFCI protection.