Inspections for the day of: Thursday, March 23, 2017.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-02256 ELE-Aging Inspection3/23/20173/23/20173/30/2017 1:31:53 PM FAIL
Unable to located contact phone number. Drove by no visible work noticed.
ELE17-00116 Electrical Rough-In3/23/20173/23/20173/23/2017 2:53:25 PMPPART
Ceiling Rough-In Inspection
Contact Jon Novak
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
3rd floor phase 1, grid as noted on contractor print rough in ok cover
ELE16-01946 Final3/22/20173/23/20173/23/2017 2:12:34 PMAFAIL
Partial Final Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Needs temp occupancy for 2nd and 4th floors. Egress lighting not complete.
210.8- GFCI protection for all receptacle outlets located 6' of sink. Both janitor basin
110.3- Outdoor receptacles not working 2 east and 1 west.
300.4-Heat trace cable shall be protected from physical damage where exposed to public in stairways and decks.
210.23(B)- 50 amp receptacles installed on 30 amp circuits for dryers on 2nd and 4th flloors.
ELE17-00052 Electrical Rough-In3/22/20173/23/20173/23/2017 10:11:56 AMAPASS
We need a ceiling inspection. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker
except kitchenette and storage rms. 1st floor grid rough in ok cover
ELE16-03753 Final3/23/20173/23/20173/23/2017 9:44:04 AMAPASS
code 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn
Final ok
ELE16-03977 Final3/23/20173/23/20173/23/2017 9:24:25 AMAPASS
code 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn
Final ok