ELE13-02256
| ELE-Aging Inspection | 3/23/2017 | 3/23/2017 | 3/30/2017 1:31:53 PM | | FAIL |
|
|
Unable to located contact phone number. Drove by no visible work noticed.
|
ELE17-00116
| Electrical Rough-In | 3/23/2017 | 3/23/2017 | 3/23/2017 2:53:25 PM | P | PART |
|
|
Ceiling Rough-In Inspection Contact Jon Novak Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek 3rd floor phase 1, grid as noted on contractor print rough in ok cover
|
ELE16-01946
| Final | 3/22/2017 | 3/23/2017 | 3/23/2017 2:12:34 PM | A | FAIL |
|
|
Partial Final Phone #: ###-#### Inspection requested via web by Kerri Hamilton Needs temp occupancy for 2nd and 4th floors. Egress lighting not complete. 210.8- GFCI protection for all receptacle outlets located 6' of sink. Both janitor basin 110.3- Outdoor receptacles not working 2 east and 1 west. 300.4-Heat trace cable shall be protected from physical damage where exposed to public in stairways and decks. 210.23(B)- 50 amp receptacles installed on 30 amp circuits for dryers on 2nd and 4th flloors.
|
ELE17-00052
| Electrical Rough-In | 3/22/2017 | 3/23/2017 | 3/23/2017 10:11:56 AM | A | PASS |
|
|
We need a ceiling inspection. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker except kitchenette and storage rms. 1st floor grid rough in ok cover
|
ELE16-03753
| Final | 3/23/2017 | 3/23/2017 | 3/23/2017 9:44:04 AM | A | PASS |
|
|
code 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
|
ELE16-03977
| Final | 3/23/2017 | 3/23/2017 | 3/23/2017 9:24:25 AM | A | PASS |
|
|
code 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
|