PLM16-02128
| PLM-Aging Inspection | 3/23/2017 | 3/23/2017 | 3/23/2017 3:04:27 PM | | PASS |
|
|
|
PLM16-02128
| Sprinkler (Final) | 3/23/2017 | 3/23/2017 | 3/23/2017 3:04:14 PM | P | PASS |
|
|
|
PLM17-00838
| Final | 3/22/2017 | 3/23/2017 | 3/23/2017 2:58:49 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Marisa Hone
|
PLM17-00869
| Water and/or Sewer | 3/23/2017 | 3/23/2017 | 3/23/2017 2:39:46 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Brett Simmons
|
PLM17-00869
| DOC - Permit Finaled | 3/23/2017 | 3/23/2017 | 3/23/2017 2:39:30 PM | P | PASS |
|
|
|
PLM17-00781
| Water Heater Final | 3/20/2017 | 3/23/2017 | 3/23/2017 2:31:57 PM | P | CANC |
|
|
Mr. Hancock has dialysis before 1 pm and after 3 pm. Please call him prior to arrival at ###-####. Phone #: ###-#### Phone #: ###-#### >> Inspection requested via web by Maira Guzman Inspection cancelled from web by: Maira Guzman
|
PLM17-00853
| Final | 3/22/2017 | 3/23/2017 | 3/23/2017 2:29:59 PM | P | PASS |
|
|
Call half hour before // Randy Phone #: ###-####
|
PLM16-03049
| Final | 3/23/2017 | 3/23/2017 | 3/23/2017 1:58:23 PM | P | FAIL |
|
|
Clint Phone #: ###-####-master bath. 1. Toilet requires a 2" vent. No vent present. 2. Dishwasher drain must rise to the top of the cabinet and drain down to the disposal. 3. Certify double check. 4. Install a combustion air inlet unrestricted into the attic at the fau. 40 sq in min.
|
PLM17-00151
| Final | 3/22/2017 | 3/23/2017 | 3/23/2017 11:46:40 AM | A | PASS |
|
|
Please contact Andy with any questions. ###-#### Phone #: ###-#### Inspection requested via web by william bouck
|
PLM17-00847
| Plumbing Rough-in | 3/22/2017 | 3/23/2017 | 3/23/2017 11:38:01 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Semsudin Konjuhovac. Failed waste pressure test
|
PLM17-00852
| Water and/or Sewer | 3/22/2017 | 3/23/2017 | 3/23/2017 11:08:14 AM | A | FAIL |
|
|
Cesar Phone #: ###-####. Water service fittings require two apposing hose clamps on each side of the fitting. Sewer ok to cover
|
PLM17-00359
| Plumbing Rough-in | 3/22/2017 | 3/23/2017 | 3/23/2017 10:30:42 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Kristy Watson. Missing nail plates and plate straps
|
PLM17-00360
| Plumbing Rough-in | 3/22/2017 | 3/23/2017 | 3/23/2017 10:30:10 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Kristy Watson. Missing nail plates and plate straps.
|
PLM17-00787
| Final | 3/22/2017 | 3/23/2017 | 3/23/2017 10:11:58 AM | A | FAIL |
|
|
Contact Jason with any questions Phone #: ###-#### Inspection requested via web by Justin Whitt. 1. Gas pressure test needs 30 psi gauge with 20 psi test. 2. Perm cap the 1/2" gas line at the unit heater. 3. Verify nail-ons are pennitraiting wood through the sheetrock. 4. Gap pressure test should have two gas valves at the pressure line.
|
PLM17-00827
| Final | 3/22/2017 | 3/23/2017 | 3/23/2017 10:09:02 AM | A | FAIL |
|
|
Contact Jason with any questions Phone #: ###-#### Inspection requested via web by Justin Whitt. 1. Install backflow assembly for the tent washer. rp. 2. Dishwasher drains needs to have an airbreak. 3. Install a pressure tank at the water heater. 4. Fix leaks in the water line. 2. Install
|
PLM17-00773
| Sprinkler (Final) | 3/22/2017 | 3/23/2017 | 3/23/2017 9:17:33 AM | A | FAIL |
|
|
David Phone #: ###-####. Backflow not pressurized or certified.
|
PLM16-04144
| Groundwork | 3/22/2017 | 3/23/2017 | 3/23/2017 9:02:49 AM | A | PART |
|
|
CHRIS IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER. kitchen and grease ok to cover
|
PLM16-04121
| Final | 3/22/2017 | 3/23/2017 | 3/23/2017 8:50:01 AM | A | FAIL |
|
|
3303 ENTER Phone #: ###-#### Inspection requested via web by Ann Marie Reyes. Certify backflow.
|
PLM17-00597
| Groundwork | 3/23/2017 | 3/23/2017 | 3/23/2017 7:52:37 AM | P | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Ann Marie Reyes Inspection cancelled from web by: Ann Marie Reyes
|