Inspections for the day of: Thursday, March 23, 2017.
Number of inspections: 10
Percentage of inspections complete: 90 %
Percentage of inspections not complete: 10 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
LIP00-00028 Child Care Renewal4/18/20163/18/2017   
BLD17-00254 FIRE-Conference3/23/20173/23/20173/23/2017 2:31:56 PMPDONE
Kevin discussed, over phone, life safety requirements. It appears a fire extinguisher is not required per IFC 906 for a U occupancy.
FIR16-00722 INSP-Sprinkler Rough-in/Hydro3/23/20173/23/20173/23/2017 1:53:24 PMPPASS
The overhead hydro tests passed.
FIR16-00722 INSP-Final Inspection3/23/20173/23/20173/23/2017 1:52:55 PMPCANC
Call/ what fits best in your schedule // Robert Phone #: ###-####
FIR17-00012 INSP-Sprinkler Rough-in3/23/20173/23/20173/23/2017 12:58:28 PMPPASS
Tenting inspection passed. Piping can be covered.
BLD17-00571 FIRE-Final Inspection3/22/20173/23/20173/23/2017 10:01:43 AMAPASS
Life safety passed
BLD17-00663 FIRE-Final Inspection3/22/20173/23/20173/23/2017 9:45:19 AMAPASS
Life safety passed. Boise Fire has also conducted inspection which passed. I tested smoke alarms, exit signs/emergency lights, and fire extinguishers are tagged and in place on both levels, Basic fire alarm system is existing.
FIR16-00284 INSP-Sprinkler Rough-in3/22/20173/23/20173/23/2017 9:03:21 AMAPASS
Unit 202 soffit piping can be covered. Rough-in passed.
BLD16-04452 FIRE-Final Inspection3/22/20173/23/20173/23/2017 9:02:54 AMAFAIL
Relay for door release did not function correctly upon activation of fire alarm.

Jason Phone #: ###-####
BLD16-00263 FIRE-Final Inspection3/22/20173/23/20173/23/2017 9:02:06 AMAFAIL
Need signage on door as discussed.

Jason Phone #: ###-####