FIR16-00491
| INSP-Final Inspection | 3/23/2017 | 3/23/2017 | 3/23/2017 4:36:14 PM | P | PART |
|
|
Partial final inspection for fire alarms complete, all associated devices for fire sprinkler systems tested excluding heat trace monitoring, this will be verified on a later inspection. Audio visual devices inspected on levels 2, 3 and 4, had a noticable audio issue at time of inspection that has apparantly been repaired, will verify audio issue has been repaired on a later inspection.
|
FIR16-00223
| INSP-Final Inspection | 3/21/2017 | 3/23/2017 | 3/23/2017 4:27:13 PM | A | PART |
|
|
Partial final inspection complete for fire sprinkler system. Fire pump commissioning is complete, dry system valve trip, low air and water flow for dry system testing complete, tamper switches and flow switches on all floors complete. Small amount of heads still need to be installed in miscellaneous spots where duct work/finish ceilings need to be installed, FIR permit will remain in issued status until remaining heads are installed and passed inspection.
|
BLD17-00169
| FIRE-Final Inspection | 3/23/2017 | 3/23/2017 | 3/23/2017 4:19:43 PM | P | PASS |
|
|
Final fire sprinkler inspection complete, no fire alarm modifications, fire extinguisher has current inspection tag and will be mounted in discussed location. Thumbturn deadbolts on suite main entry doors will be removed before final building inspection. Final life fire safety inspection passed/complete.
|
FIR17-00076
| INSP-Final Inspection | 3/23/2017 | 3/23/2017 | 3/23/2017 4:17:30 PM | P | PASS |
|
|
Final fire sprinkler inspection passed/complete
|
BLD17-00073
| FIRE-Final Inspection | 3/23/2017 | 3/23/2017 | 3/23/2017 4:14:52 PM | P | CANC |
|
|
Inspection request is for a different BLD permit associated with the same building address, thie request is cancelled.
|
BLD15-04468
| FIRE-Conference | 3/23/2017 | 3/23/2017 | 3/23/2017 1:30:10 PM | P | DONE |
|
|
Fire conference complete
|
FIR16-00606
| INSP-Sprinkler Rough-in | 3/21/2017 | 3/23/2017 | 3/23/2017 12:11:07 PM | A | CANC |
|
|
Called point of contact at phone number provided, Carlos Phone #: ###-#### three times to coordinate a meeting place, left a message on the first attempt, no return call recieved by 12:10pm, this request is cancelled, contractor will need to reschedule.
|
FIR16-00223
| INSP-Sprinkler Rough-in/Hydro | 3/23/2017 | 3/23/2017 | 3/23/2017 11:25:13 AM | A | PASS |
|
|
Hydrostatic testing for overhead fire sprinkler piping complete for entire scope of work.
|
BLD15-01115
| FIRE-Final Inspection | 3/22/2017 | 3/23/2017 | 3/23/2017 11:03:34 AM | A | PASS |
|
|
Final life fire safety inspection passed/complete
|
BLD15-01112
| FIRE-Final Inspection | 3/22/2017 | 3/23/2017 | 3/23/2017 11:03:13 AM | A | PASS |
|
|
Final life fire safety inspection passed/complete
|
FIR17-00119
| INSP-Sprinkler Rough-in | 3/23/2017 | 3/23/2017 | 3/23/2017 11:02:30 AM | P | CANC |
|
|
Scheduled for 24MAR2017
|
BLD15-01110
| FIRE-Final Inspection | 3/22/2017 | 3/23/2017 | 3/23/2017 8:27:10 AM | A | PASS |
|
|
Previous issues with fire alarm system have been resolved, final life fire safety inspection passed/complete.
|
BLD15-04468
| FIRE-Conference | 3/22/2017 | 3/23/2017 | 3/23/2017 8:24:49 AM | A | CANC |
|
|
|
BLD15-01111
| FIRE-Final Inspection | 3/22/2017 | 3/23/2017 | 3/23/2017 8:04:13 AM | A | CANC |
|
|
Life fire safety inspection was completed on 2/16/2017 per notes in activities.
|
FIR17-00130
| INSP-Supply line flush | 3/21/2017 | 3/23/2017 | 3/21/2017 10:38:15 AM | P | CANC |
|
|
Underground rough/hydro. Call Jake when heading out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
|
FIR16-00760
| INSP-Sprinkler Rough-in/Hydro | 3/20/2017 | 3/23/2017 | 3/21/2017 10:38:13 AM | P | CANC |
|
|
Underground rough/hydro - call Jake when heading out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
|
FIR17-00001
| INSP-Supply line flush | 3/20/2017 | 3/23/2017 | 3/21/2017 10:38:11 AM | P | CANC |
|
|
Underground rough/hydro - call Jake when heading out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
|