Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00491 INSP-Final Inspection3/23/20173/23/20173/23/2017 4:36:14 PMPPART
Partial final inspection for fire alarms complete, all associated devices for fire sprinkler systems tested excluding heat trace monitoring, this will be verified on a later inspection. Audio visual devices inspected on levels 2, 3 and 4, had a noticable audio issue at time of inspection that has apparantly been repaired, will verify audio issue has been repaired on a later inspection.
FIR16-00223 INSP-Final Inspection3/21/20173/23/20173/23/2017 4:27:13 PMAPART
Partial final inspection complete for fire sprinkler system. Fire pump commissioning is complete, dry system valve trip, low air and water flow for dry system testing complete, tamper switches and flow switches on all floors complete. Small amount of heads still need to be installed in miscellaneous spots where duct work/finish ceilings need to be installed, FIR permit will remain in issued status until remaining heads are installed and passed inspection.
BLD17-00169 FIRE-Final Inspection3/23/20173/23/20173/23/2017 4:19:43 PMPPASS
Final fire sprinkler inspection complete, no fire alarm modifications, fire extinguisher has current inspection tag and will be mounted in discussed location. Thumbturn deadbolts on suite main entry doors will be removed before final building inspection. Final life fire safety inspection passed/complete.
FIR17-00076 INSP-Final Inspection3/23/20173/23/20173/23/2017 4:17:30 PMPPASS
Final fire sprinkler inspection passed/complete
BLD17-00073 FIRE-Final Inspection3/23/20173/23/20173/23/2017 4:14:52 PMPCANC
Inspection request is for a different BLD permit associated with the same building address, thie request is cancelled.
BLD15-04468 FIRE-Conference3/23/20173/23/20173/23/2017 1:30:10 PMPDONE
Fire conference complete
FIR16-00606 INSP-Sprinkler Rough-in3/21/20173/23/20173/23/2017 12:11:07 PMACANC
Called point of contact at phone number provided, Carlos Phone #: ###-#### three times to coordinate a meeting place, left a message on the first attempt, no return call recieved by 12:10pm, this request is cancelled, contractor will need to reschedule.
FIR16-00223 INSP-Sprinkler Rough-in/Hydro3/23/20173/23/20173/23/2017 11:25:13 AMAPASS
Hydrostatic testing for overhead fire sprinkler piping complete for entire scope of work.
BLD15-01115 FIRE-Final Inspection3/22/20173/23/20173/23/2017 11:03:34 AMAPASS
Final life fire safety inspection passed/complete
BLD15-01112 FIRE-Final Inspection3/22/20173/23/20173/23/2017 11:03:13 AMAPASS
Final life fire safety inspection passed/complete
FIR17-00119 INSP-Sprinkler Rough-in3/23/20173/23/20173/23/2017 11:02:30 AMPCANC
Scheduled for 24MAR2017
BLD15-01110 FIRE-Final Inspection3/22/20173/23/20173/23/2017 8:27:10 AMAPASS
Previous issues with fire alarm system have been resolved, final life fire safety inspection passed/complete.
BLD15-04468 FIRE-Conference3/22/20173/23/20173/23/2017 8:24:49 AMACANC
BLD15-01111 FIRE-Final Inspection3/22/20173/23/20173/23/2017 8:04:13 AMACANC
Life fire safety inspection was completed on 2/16/2017 per notes in activities.
FIR17-00130 INSP-Supply line flush3/21/20173/23/20173/21/2017 10:38:15 AMPCANC
Underground rough/hydro. Call Jake when heading out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
FIR16-00760 INSP-Sprinkler Rough-in/Hydro3/20/20173/23/20173/21/2017 10:38:13 AMPCANC
Underground rough/hydro - call Jake when heading out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
FIR17-00001 INSP-Supply line flush3/20/20173/23/20173/21/2017 10:38:11 AMPCANC
Underground rough/hydro - call Jake when heading out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello