FIR12-00309
| FIR-Aging Inspection | 3/23/2018 | 3/23/2018 | 3/28/2018 10:25:33 AM | | DONE |
|
|
Sent a follow up message with Fire Alarm Technician, Brian at phone# ###-####, to try and get this inspection completed and finaled.
|
FIR17-00267
| INSP-Sprinkler Rough-in | 3/23/2018 | 3/23/2018 | 3/23/2018 1:33:45 PM | P | PART |
|
|
Rough to cover inspection for levels 4 and 5 corridors complete, approved for cover.
|
FIR17-00734
| INSP-Sprinkler Rough-in | 3/22/2018 | 3/23/2018 | 3/23/2018 1:33:00 PM | P | PART |
|
|
Submit documentation supporting the point of attachment to Z-purlins for sway brace attachment. Submit documentation supporting the use of Sammy's being installed on the bottom of the Z-purlin instead of the side. Sway braces cannot be attached to each other, provide pipe clamps/quick clamps for each individual sway brace sprinkler main attachment.. Rough to cover inspection complete for office area levels 1 and 2, if bottom of purlin hanger attachment is not approved then hangers installed of purlin will need to be changed.
|
BLD17-03115
| FIRE-Final Inspection | 3/22/2018 | 3/23/2018 | 3/23/2018 11:47:55 AM | A | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguisher is in place with a current inspection tag. Final life fire safety inspection complete.
|
FIR17-00587
| INSP-Supply line flush | 3/22/2018 | 3/23/2018 | 3/23/2018 11:36:40 AM | A | DONE |
|
|
Underground main line flush complete.
|
BLD18-00927
| FIRE-Final Inspection | 3/21/2018 | 3/23/2018 | 3/23/2018 10:33:23 AM | A | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguisher is in place with a current inspection tag. Final life fire safety inspection complete.
|
FIR17-00594
| INSP-Final Inspection | 3/23/2018 | 3/23/2018 | 3/23/2018 10:21:35 AM | P | PASS |
|
|
O-ring type heads have been replaced in area of work, final fire sprinkler inspection for area of work complete.
|
BLD17-03755
| FIRE-Final Inspection | 3/22/2018 | 3/23/2018 | 3/23/2018 9:07:53 AM | A | PASS |
|
|
Only fire sprinkler in tenant space is in gas closet (gas closet is existing, room appears to be rated with a self closing door, tanks are sucure), no other fire sprinklers, no fire alarms, fire extinguishers are in place and will be tagged with current inspection tags. Final life fire safety inspection for area of work complete.
|