Inspections for the day of: Friday, March 23, 2018.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00309 FIR-Aging Inspection3/23/20183/23/20183/28/2018 10:25:33 AM DONE
Sent a follow up message with Fire Alarm Technician, Brian at phone# ###-####, to try and get this inspection completed and finaled.
FIR17-00267 INSP-Sprinkler Rough-in3/23/20183/23/20183/23/2018 1:33:45 PMPPART
Rough to cover inspection for levels 4 and 5 corridors complete, approved for cover.
FIR17-00734 INSP-Sprinkler Rough-in3/22/20183/23/20183/23/2018 1:33:00 PMPPART
Submit documentation supporting the point of attachment to Z-purlins for sway brace attachment. Submit documentation supporting the use of Sammy's being installed on the bottom of the Z-purlin instead of the side. Sway braces cannot be attached to each other, provide pipe clamps/quick clamps for each individual sway brace sprinkler main attachment.. Rough to cover inspection complete for office area levels 1 and 2, if bottom of purlin hanger attachment is not approved then hangers installed of purlin will need to be changed.
BLD17-03115 FIRE-Final Inspection3/22/20183/23/20183/23/2018 11:47:55 AMAPASS
No fire sprinklers, no fire alarms, fire extinguisher is in place with a current inspection tag. Final life fire safety inspection complete.
FIR17-00587 INSP-Supply line flush3/22/20183/23/20183/23/2018 11:36:40 AMADONE
Underground main line flush complete.
BLD18-00927 FIRE-Final Inspection3/21/20183/23/20183/23/2018 10:33:23 AMAPASS
No fire sprinklers, no fire alarms, fire extinguisher is in place with a current inspection tag. Final life fire safety inspection complete.
FIR17-00594 INSP-Final Inspection3/23/20183/23/20183/23/2018 10:21:35 AMPPASS
O-ring type heads have been replaced in area of work, final fire sprinkler inspection for area of work complete.
BLD17-03755 FIRE-Final Inspection3/22/20183/23/20183/23/2018 9:07:53 AMAPASS
Only fire sprinkler in tenant space is in gas closet (gas closet is existing, room appears to be rated with a self closing door, tanks are sucure), no other fire sprinklers, no fire alarms, fire extinguishers are in place and will be tagged with current inspection tags. Final life fire safety inspection for area of work complete.