BLD19-03606
| FIRE-Conference | 3/23/2020 | 3/23/2020 | 3/23/2020 11:45:34 AM | P | DONE |
|
|
Fire conference is complete.
Kevin Phone #: ###-####
|
FIR19-00855
| INSP-Final Inspection | 3/23/2020 | 3/23/2020 | 3/23/2020 9:44:06 AM | A | FAIL |
|
|
Freeze protection/tenting no installed over new drop and piping to added head in washer/dryer closet, no cover until freeze protection is provided.
Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR19-00521
| INSP-Final Inspection | 3/23/2020 | 3/23/2020 | 3/23/2020 9:18:36 AM | A | FAIL |
|
|
Bell needs to be moved closer to front of house as discussed. Could not rest irrigation shutdown during water flow, no zones hooked up.
Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
BLD19-04789
| FIRE-Final Inspection | 3/16/2020 | 3/23/2020 | 3/23/2020 8:48:45 AM | A | FAIL |
|
|
Thumb-turn deadnolts are installed on the north and east egress doors, provide code compliant door hardware for noted doors.
Brandenburg Phone #: ###-####
|