Inspections for the day of: Wednesday, March 24, 2004.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorPat Lass
TitleELE-INSPECTOR
Phone #794-9478
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE04-00786 Rough-In Permanent Service3/23/20043/24/20043/24/2004 12:00:00 AMAPART
###-####. Scheduled by a contractor via Hello! on 3/23/2004 at 11:57:59 AM. Contact: ###-####. 3/24/2004 7:39:22 AM
R/I Ok
install concrete encased electrode 3/24/2004 9:12:15 AM
ELE04-00808 Permanent Service3/23/20043/24/20043/24/2004 12:00:00 AMAPART
###-#### derek
requires 2nd ground rod.
water bonding is ok.
will change panel to junction box and run 4 wire to range.
P/S O/H R Ok to transfer power 3/24/2004 8:47:30 AM
ELE04-00175 Final3/23/20043/24/20043/24/2004 12:00:00 AMAPASS
chris; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
ELE04-00410 Final3/24/20043/24/20043/24/2004 12:00:00 AMPPASS
darrell- ###-#### -also for detached gar
ELE04-00814 Rough-In Permanent Service3/24/20043/24/20043/24/2004 12:00:00 AMPFAIL
Dan; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
bond nipple between meter and panel.
concrete electrode required.
secure raceways at service within 3 ft.
arrange flex to recep under panel to drain.
bond water piping system. 3/24/2004 3:24:11 PM
ELE04-00091 Electrical Rough-In3/24/20043/24/20043/24/2004 12:00:00 AMPPASS
Charlie; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
large junction box in basement has ampacity rerate problem and grounding to be checked 3/24/2004 2:26:37 PM
ELE03-03799 Permanent Service3/24/20043/24/20043/24/2004 12:00:00 AMPNR
no service requested or permitted 3/24/2004 12:33:48 PM