Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00737 INSP-Sprinkler Rough-in/Hydro3/24/20053/24/20053/24/2005 12:00:00 AMACANC
Contact: Terry - Cover Inspection; Phone #: ###-#### Duplicate inspection. 3/24/2005 9:31:26 AM
FIR04-00737 INSP-Sprinkler Rough-in3/23/20053/24/20053/24/2005 12:00:00 AMAPART
terry; Phone #: ###-#### Dry system east side project ok to cover. 3/24/2005 9:27:17 AM
FIR04-00788 INSP-Alarm Testing3/23/20053/24/20053/24/2005 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 3/23/2005 at 2:48:16 PM. Contact: ###-####. Smoke detectors operated door, but signals did not report to central station. Need to re -test. 3/24/2005 9:36:55 AM
BLD02-03021 FIRE-Final Inspection3/23/20053/24/20053/24/2005 12:00:00 AMACANC
284=5170 - carl
BLD02-03020 FIRE-Final Inspection3/23/20053/24/20053/24/2005 12:00:00 AMACANC
###-#### - carl
BLD02-03019 FIRE-Final Inspection3/23/20053/24/20053/24/2005 12:00:00 AMACANC
###-#### - carl
FIR05-00057 INSP-Sprinkler Rough-in/Hydro3/24/20053/24/20053/24/2005 12:00:00 AMPPASS
hydro test passed 3/24/2005 3:57:02 PM
FIR04-00258 INSP-Sprinkler Rough-in/Hydro3/24/20053/24/20053/24/2005 12:00:00 AMPPASS
Phone #: ###-#### Skylights ok to cover in south center and northeast areas. See approved plans for exact lacation. 3/24/2005 12:42:45 PM
FIR05-00103 INSP-Sprinkler Rough-in3/24/20053/24/20053/24/2005 12:00:00 AMPPART
Ok to bury piping except areas for thrust blocks. 3/24/2005 3:59:03 PM
FIR05-00010 INSP-Final Inspection3/24/20053/24/20053/24/2005 12:00:00 AMPFAIL
Leroy; Phone #: ###-#### Permit not ready for final. Inspection for rough in to cover ok except for proper temp. head placement verification in high areas and next to heat vents. 3/24/2005 11:28:05 AM
FIR03-00796 INSP-Sprinkler Rough-in/Hydro3/24/20053/24/20053/24/2005 12:00:00 AMPPASS
fire alarm finaled 3/24/2005 1:14:14 PM
BLD04-01474 FIRE-Final Inspection3/24/20053/24/20053/24/2005 12:00:00 AMPFAIL
Only thing corrected was door adjustments 3/24/2005 4:02:30 PM
FIR05-00147 INSP-Final Inspection3/24/20053/24/20053/24/2005 12:00:00 AMPPASS
Joe; Phone #: ###-#### Hood suppresion system operated correctly. Permit finaled. 3/24/2005 1:33:14 PM
BLD04-02778 FIRE-Final Inspection3/24/20053/24/20053/24/2005 12:00:00 AMPPASS
fire life safety finaled. Dave Hannah verified. 3/24/2005 2:01:15 PM
BLD04-00958 FIRE-Final Inspection3/24/20053/24/20053/24/2005 12:00:00 AMPPASS
fire life safety finaled