ELE05-03831
| ELE-Aging Inspection | 3/24/2006 | 3/24/2006 | 3/30/2006 3:48:13 PM | | DONE |
|
|
|
ELE05-04252
| ELE-Aging Inspection | 3/24/2006 | 3/24/2006 | 3/27/2006 9:13:06 AM | | CANC |
|
|
|
ELE05-04600
| Electrical Rough-In | 3/24/2006 | 3/24/2006 | 3/24/2006 4:43:04 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 3/24/2006 at 7:17:34 AM. Contact: ###-####. east half walls , needs permit for each tennant space
|
ELE06-01014
| Final | 3/24/2006 | 3/24/2006 | 3/24/2006 4:42:01 PM | P | PASS |
|
|
We installed a new 30 amp 4 wire dryer receptacle below panel. Check in at the receptionist desk and they will direct you to the electrical panel.(#6030223hms). Jman/Craig###-####.Thanks!!! Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ok owner moved dryer while I was there so panels have clearence
|
ELE06-00984
| Permanent Service | 3/22/2006 | 3/24/2006 | 3/24/2006 3:50:11 PM | P | FAIL |
|
|
###-#### corr. met owner, 312.5(A) conn for GEC, 110.3(A) only 1 wire under each grd clamp also istall wires in clamp properly , also 1 wire per lug in panel grd wire solid and stranded, 230.28 guy kit mast, meter too high, 300.10 nipple between meter and panel needs 4 locknuts
|
ELE06-01007
| Final | 3/24/2006 | 3/24/2006 | 3/24/2006 3:07:07 PM | P | PASS |
|
|
Pat; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong ok
|
ELE06-00937
| Electrical Rough-In | 3/24/2006 | 3/24/2006 | 3/24/2006 2:36:29 PM | P | PASS |
|
|
HZ -- reinspection; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong ok
|
ELE06-00602
| Electrical Rough-In | 3/24/2006 | 3/24/2006 | 3/24/2006 2:06:25 PM | P | PASS |
|
|
need rough in on basement remodel, thank you; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH met with Brian, r/i ok shall address grd wire and bonding at service, wire fill in wiremold, and box fill in storage rm, 1 box
|
ELE06-00085
| Final | 3/24/2006 | 3/24/2006 | 3/24/2006 12:56:11 PM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 3/24/2006 at 6:07:41 AM. Contact: ###-####. corr. posted called 110.26(F)(1) required space sub panel for hot water system laundry rm, 110.3 shall follow all manufactures instructions for hot water system min #6 wire, min. breaker 60 amp,220.40 shall calc service and feeder to hot water system sub panel both of them too small , 250.118 (5) both flexes at hot water system need equip grds
|
ELE05-03697
| Final | 3/23/2006 | 3/24/2006 | 3/24/2006 10:36:15 AM | A | PASS |
|
|
David; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong ok
|
ELE06-00602
| Electrical Rough-In | 3/22/2006 | 3/24/2006 | 3/24/2006 9:59:21 AM | A | PART |
|
|
need rough in on basement remodel. thank you.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH called need to met contractor
|
ELE06-00980
| Final | 3/23/2006 | 3/24/2006 | 3/24/2006 9:14:54 AM | A | PASS |
|
|
NEED FINAL INSPECTION ON COOL PED INSTALLATION. THANK YOU.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH
|
ELE06-00980
| Permanent Service | 3/24/2006 | 3/24/2006 | 3/24/2006 9:14:44 AM | A | PASS |
|
|
NEED FINAL INSPECTION ON COOL PED INSTALLATION. THANK YOU.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH p/s u/g new ok
|
ELE06-00916
| Electrical Rough-In | 3/22/2006 | 3/24/2006 | 3/24/2006 8:47:09 AM | A | FAIL |
|
|
dave; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa corr. met contractor, BCC no violations retained 110.3 use manufactures listed breakers only, 300.4 11/4" , 330.30 STRAP MC within 12" of boxes and panels
|