Inspections for the day of: Friday, March 24, 2006.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-03831 ELE-Aging Inspection3/24/20063/24/20063/30/2006 3:48:13 PM DONE
ELE05-04252 ELE-Aging Inspection3/24/20063/24/20063/27/2006 9:13:06 AM CANC
ELE05-04600 Electrical Rough-In3/24/20063/24/20063/24/2006 4:43:04 PMPPASS
Scheduled by a contractor via Hello! on 3/24/2006 at 7:17:34 AM. Contact: ###-####. east half walls , needs permit for each tennant space
ELE06-01014 Final3/24/20063/24/20063/24/2006 4:42:01 PMPPASS
We installed a new 30 amp 4 wire dryer receptacle below panel. Check in at the receptionist desk and they will direct you to the electrical panel.(#6030223hms).
Jman/Craig###-####.Thanks!!! Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell
ok owner moved dryer while I was there so panels have clearence
ELE06-00984 Permanent Service3/22/20063/24/20063/24/2006 3:50:11 PMPFAIL
###-#### corr. met owner, 312.5(A) conn for GEC, 110.3(A) only 1 wire under each grd clamp also istall wires in clamp properly , also 1 wire per lug in panel grd wire solid and stranded, 230.28 guy kit mast, meter too high, 300.10 nipple between meter and panel needs 4 locknuts
ELE06-01007 Final3/24/20063/24/20063/24/2006 3:07:07 PMPPASS
Pat; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong ok
ELE06-00937 Electrical Rough-In3/24/20063/24/20063/24/2006 2:36:29 PMPPASS
HZ -- reinspection; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong ok
ELE06-00602 Electrical Rough-In3/24/20063/24/20063/24/2006 2:06:25 PMPPASS
need rough in on basement remodel, thank you; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH
met with Brian, r/i ok shall address grd wire and bonding at service, wire fill in wiremold, and box fill in storage rm, 1 box
ELE06-00085 Final3/24/20063/24/20063/24/2006 12:56:11 PMPFAIL
Scheduled by a contractor via Hello! on 3/24/2006 at 6:07:41 AM. Contact: ###-####. corr. posted called 110.26(F)(1) required space sub panel for hot water system laundry rm, 110.3 shall follow all manufactures instructions for hot water system min #6 wire, min. breaker 60 amp,220.40 shall calc service and feeder to hot water system sub panel both of them too small , 250.118 (5) both flexes at hot water system need equip grds
ELE05-03697 Final3/23/20063/24/20063/24/2006 10:36:15 AMAPASS
David; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong
ok
ELE06-00602 Electrical Rough-In3/22/20063/24/20063/24/2006 9:59:21 AMAPART
need rough in on basement remodel. thank you.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH called need to met contractor
ELE06-00980 Final3/23/20063/24/20063/24/2006 9:14:54 AMAPASS
NEED FINAL INSPECTION ON COOL PED INSTALLATION. THANK YOU.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH
ELE06-00980 Permanent Service3/24/20063/24/20063/24/2006 9:14:44 AMAPASS
NEED FINAL INSPECTION ON COOL PED INSTALLATION. THANK YOU.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH p/s u/g new ok
ELE06-00916 Electrical Rough-In3/22/20063/24/20063/24/2006 8:47:09 AMAFAIL
dave; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
corr. met contractor, BCC no violations retained 110.3 use manufactures listed breakers only, 300.4 11/4" , 330.30 STRAP MC within 12" of boxes and panels