Inspections for the day of: Friday, March 24, 2006.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-00756 Electrical Rough-In3/24/20063/24/20063/24/2006 4:29:17 PMPFAIL
This inspection was missed on the first request, and we are requesting a re-inspection.; Phone #: ###-#### Internet Inspection Request from: Justin Metcalf called contr, left corr notice, fee due, 312.5 all conductors entering enclosures shall have abrasion protection, 110.12(C) there shall be no bent parts (door hinges), 408.4 circuit directory shall be provided, 406(B)(2)(a)receptacle shall have weatherproof cover for in-use, 250.53(G) electrode shall not be driven over 45 degree angle
ELE05-04100 Final3/24/20063/24/20063/24/2006 3:54:35 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot called contr, left corr notice, 314.23(C) receptacle outlets shall be securely fastened in place, 210.52(A) receptacles shall be added in kitchen countertop area and library room, 406.8(C) receptacles shall not be installed over a bathtub
ELE05-03919 Permanent Service3/23/20063/24/20063/24/2006 3:10:48 PMPPASS
PLEASE CALL DAVE BRADSHAW TO MEET INSPECTOR ON SITE; Phone #: ###-#### Internet Inspection Request from: Randy Vail looked at fittings, ok, p/s, unit 7009 ok for meter
ELE06-01010 Temporary Service3/24/20063/24/20063/24/2006 2:29:48 PMPPASS
overhead service; Phone #: ###-#### Internet Inspection Request from: Latisha Peltier t/s o/h n ok
ELE06-00915 Final3/24/20063/24/20063/24/2006 1:44:58 PMPPASS
dave ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called contr to put bushing on gec, ok to final
ELE06-01016 Permanent Service3/24/20063/24/20063/24/2006 1:03:22 PMPFAIL
kelley falin ###-#### or ###-#### called contr, left corr notice,240.81 circuit bkr handle shall be on in up position, 312.5 abrasion protection shall be provided for all conductors entering enclosures,250.24(1) gndg electrode conductor shall connect to grounded conductor terminal, 314.15(A) coupling shall be listed for use in wet location, 230.66 service equip shall be marked to identify as being suitable for use as service equipment
ELE06-00965 Temporary Service3/23/20063/24/20063/24/2006 10:45:45 AMAPASS
Scheduled by a contractor via Hello! on 3/23/2006 at 2:41:47 PM. Contact: ###-####. corr made, t/s u/g n ok
ELE06-00966 Temporary Service3/23/20063/24/20063/24/2006 10:45:04 AMAPASS
Scheduled by a contractor via Hello! on 3/23/2006 at 3:00:27 PM. Contact: ###-####. corr made, t/s u/g n ok
ELE06-00963 Temporary Service3/23/20063/24/20063/24/2006 10:44:28 AMAPASS
Scheduled by a contractor via Hello! on 3/23/2006 at 2:40:47 PM. Contact: ###-####. corr made, t/s u/g n ok
ELE06-00962 Temporary Service3/23/20063/24/20063/24/2006 10:42:15 AMAPASS
Scheduled by a contractor via Hello! on 3/23/2006 at 2:40:16 PM. Contact: ###-####. corr made, t/s u/g n ok
ELE06-00964 Temporary Service3/23/20063/24/20063/24/2006 10:40:59 AMAPASS
Scheduled by a contractor via Hello! on 3/23/2006 at 2:41:17 PM. Contact: ###-####. corr made, t/s u/g n ok
ELE06-00961 Temporary Service3/23/20063/24/20063/24/2006 10:40:16 AMAPASS
Scheduled by a contractor via Hello! on 3/23/2006 at 2:36:56 PM. Contact: ###-####. corr made, t/s u/g n ok
ELE05-04649 ELE-Aging Inspection3/24/20063/24/20063/24/2006 9:39:07 AM DONE
see final
ELE05-04649 Final3/24/20063/24/20063/24/2006 9:38:48 AMAPASS
ok to final
ELE06-00078 ELE-Aging Inspection3/24/20063/24/20063/24/2006 9:24:07 AM DONE
checked job, suc
ELE06-00790 Electrical Rough-In3/22/20063/24/20063/24/2006 8:49:21 AMAPART
RI partial walls. Thanks!; Phone #: ###-#### Internet Inspection Request from: Heather Packer met contr, left corr notice, 110.26(F)(1)(a) the space equal to the width and depth of the equipment and extending from the floor to the structural ceiling shall be dedicated to the electrical installation, BCC u/g shall be inspected before cover, interior walls except at panel area ok to cover anop