Inspections for the day of: Monday, March 24, 2008.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-00276 Final3/24/20083/24/20083/24/2008 4:08:45 PMPPASS
anill Phone #: ###-#### corrections made, ok to final
ELE07-01851 Electrical Rough-In3/24/20083/24/20083/24/2008 3:43:13 PMPFAIL
russ Phone #: ###-#### met owner, told BCC all make-up shall be done
ELE08-00604 Electrical Rough-In3/24/20083/24/20083/24/2008 3:11:16 PMPPASS
Phone #: ###-#### Internet Inspection Request from: BRENDA HURST walls only ok to cover
ELE08-00417 Electrical Rough-In3/24/20083/24/20083/24/2008 2:11:20 PMPPASS
todd Phone #: ###-#### or ###-#### ric ok
ELE08-00669 Electrical Rough-In3/21/20083/24/20083/24/2008 1:29:08 PMPPASS
zane Phone #: ###-#### ric ok
ELE07-02082 Electrical Rough-In3/24/20083/24/20083/24/2008 12:52:19 PMPFAIL
steve Phone #: ###-#### met owner , corrections, NEC 210.52 outlet spacing shall be wothin 6' in wall space, 110.12(C) there shall be no broken boxes,BCC all make-up shall be done
ELE08-00679 Conference3/21/20083/24/20083/24/2008 10:10:41 AMADONE
Gary ###-#### xt.3706 //please call for access info (already started work) talked about u/g inspection, 4-90degree bends, opening trench, no insulation at bored holes, grounding and circuits for garage
ELE08-00637 Electrical Rough-In3/22/20083/24/20083/24/2008 9:55:21 AMAFAIL
Scheduled by a contractor via Hello! on 3/22/2008 at 7:46:56 PM. Contact: ###-####. met owner, left correction notice, NEC 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing member. 312.5 shall close openings in boxes and use abrasion protection, 300.14 at least 6" free conductor shall be provided where conductor enters box then spliced, 210.52(A)(1) receptacles shall be installed such that no point along floor line is more than 6' from an outlet, 334.30 nm cable shall be secured at 4 1/2' intervals, 314.17 nm cable shall be secured within 8" of box BCC all make-up shall be done
ELE08-00675 Electrical Rough-In3/20/20083/24/20083/24/2008 9:34:16 AMAFAIL
kenneth Phone #: ###-#### called left correction notice, NEC 300.4(A)&(D) raceways shall be 1/14" from edge of framing members and bored holes, BCC raceways shall not be run in valley of 2x4 studs
ELE08-00679 Electrical Rough-In3/21/20083/24/20083/24/2008 9:00:48 AMAFAIL
Gary ###-#### xt. 3706//please call for access info met owner, BCC all u/g shall be inspected before cover, make-up shall be done, foam at header shall be removed for inspection
ELE08-00671 Electrical Rough-In3/21/20083/24/20083/24/2008 8:07:33 AMAPASS
Stratton and Assosiates corner 8th and Front bathroom addtion. Thank you Phone #: ###-#### Internet Inspection Request from: Daniel Gamboa called contractor ri ok walls and hard lids