FIR07-00972
| INSP-Final Inspection | 3/24/2008 | 3/24/2008 | 3/25/2008 4:05:51 PM | P | FAIL |
|
|
No access to tenant. I spoke to todd with simplexgrinnell and he is tracking down the owner/tenant to get access in.
|
BLD05-02539
| FIRE-Final Inspection | 3/24/2008 | 3/24/2008 | 3/24/2008 6:32:48 PM | P | PART |
|
|
A temporary occupancy was given, with dave hannimans permission, until the fire lane to the northwest has been completed. All other items are passed.
|
FIR07-00546
| INSP-Final Inspection | 3/24/2008 | 3/24/2008 | 3/24/2008 6:31:37 PM | P | PASS |
|
|
Permit finaled
|
FIR07-00461
| INSP-Sprinkler Rough-in | 3/20/2008 | 3/24/2008 | 3/24/2008 2:40:33 PM | A | FAIL |
|
|
This inspection was for an underground flush. The contractor had set up the flush through a 2 1/2" hose. The system riser is 4". Without a pito guage the actual flow could not be verified so no flush was performed. The underground flush shall conform to NFPA 13 10.10.2.1.3.
|
BLD05-01395
| FIRE-Final Inspection | 3/21/2008 | 3/24/2008 | 3/24/2008 2:37:03 PM | A | PASS |
|
|
Life safety passed
|
FIR08-00200
| INSP-Sprinkler Rough-in | 3/21/2008 | 3/24/2008 | 3/24/2008 11:45:46 AM | A | PASS |
|
|
Sprinkler piping is ok to cover
|
BLD07-03213
| FIRE-Final Inspection | 3/20/2008 | 3/24/2008 | 3/20/2008 1:36:56 PM | A | CANC |
|
|
todd - fire life safety Phone #: ###-#### Inspection cancelled from web by: Patricia Smith
|