BLD06-03634
| FIRE-Final Inspection | 3/24/2010 | 3/24/2010 | 3/24/2010 5:09:09 PM | P | PASS |
|
|
Noted corrections are finished per activity notes on project related FIR and BLD permits.
|
FIR02-00018
| FIR-Aging Inspection | 3/24/2010 | 3/24/2010 | 3/24/2010 5:01:13 PM | P | DONE |
|
|
Work for this space appears to have been completed under a separate permit- ref. BLD01-00822.
|
BLD10-00368
| FIRE-Conference | 3/24/2010 | 3/24/2010 | 3/24/2010 4:57:24 PM | P | DONE |
|
|
On site visit regarding fire life safety inspection items including exit signs, EM lights, door hardware, etc.
|
FIR10-00097
| INSP-Final Inspection | 3/24/2010 | 3/24/2010 | 3/24/2010 4:56:07 PM | P | PASS |
|
|
Fire sprinkler permit work passed final inspection, one existing "loaded" pendent adjacent to an HVAC diffuser cleaned while on site. Permit finaled.
|
FIR10-00042
| INSP-Final Inspection | 3/24/2010 | 3/24/2010 | 3/24/2010 4:52:04 PM | P | PART |
|
|
Final pending protection of piping from corrosion where exposed at the outside of the building per NFPA 13 ch. 8 as discussed, also need to provide spare sprinkler stock of the new type installed at the head box. Remainder of overhead modifications and rough-in per the scope of work are satisfactory.
|
FIR09-00645
| INSP-Final Inspection | 3/23/2010 | 3/24/2010 | 3/24/2010 10:11:27 AM | A | CANC |
|
|
Tim Christopherson
has to be between 10AM and 12noon for customer Inspection requested from web by: Diane Turner Phone #: ###-#### Inspection cancelled from web by: Diane Turner
|
FIR09-00643
| INSP-Final Inspection | 3/23/2010 | 3/24/2010 | 3/24/2010 10:11:08 AM | A | CANC |
|
|
Tim Christopherson
has to be between 10AM and 12AM Inspection requested from web by: Diane Turner Phone #: ###-#### Inspection cancelled from web by: Diane Turner
|